LG AMNH096BTG0 Manuals page 195

Multi type air conditioner
Hide thumbs Also See for AMNH096BTG0:
Table of Contents

Advertisement

I Error Indicator (Outdoor)
Outdoor Error
Error
Contents
code
40
CT Circuit
41
D-pipe sensor INV. (open/ short)
44
Air sensor (open/ short)
45
Cond. Pipe sensor (open/ short)
46
Suction pipe sensor (open/ short)
47
D-pipe sensor Cons. (open/ short)
51
Over capacity
53
Communication (Indoor
60
EEPROM check sum
61
Cond. Pipe sensor temp. high
62
Heat sink sensor temp. high
65
Heat sink sensor (open/ short)
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LED02G
LED01G
(Green)
(Red)
4 times
4 times
1 time
4 times
4 times
4 times
5 times
4 times
6 times
4 times
7 times
5 times
1 times
Outdoor)
5 times
3 times
6 times
6 times
1 time
6 times
2 times
6 times
5 times
- 195 -
Troubleshooting Guide
Case of error
CT Circuit malfunction
Open / Short
Open / Short
Open / Short
Open / Short
Open / Short
Over combination
Communication Poorly
Check sum mismatching
Cond. Temp. high
Heat sink temp. high
Open / Short
LGE Internal Use Only
Outdoor
Status
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off

Hide quick links: