Control circuit specifications
2.3.5

When connecting the operation panel using a connection cable

Having an operation panel on the enclosure surface is convenient. With a connection cable, you can mount the
operation panel (FR-DU07) to the enclosure surface, and connect it to the inverter.
Operation panel(FR-DU07)
REMARKS
· Overall wiring length when the operation panel is connected: 20m(65.6 feet)
· Refer to the following when fabricating the cable on the user side.
Commercially available product examples
(as of Oct. 2008)
Product
1) Communication cable
2) RJ-45 connector
* Do not use pins No. 2, 8 of the communication cable.
Refer to page 200 for RS-485 communication.
34
Parameter unit connection cable
(FR-CB2
)(option)
Operation panel connection connector
(FR-ADP)(option)
Type
SGLPEV-T (Cat5e/300m)
24AWG × 4P*
5-554720-3
Maker
Mitsubishi Cable Industries, Ltd.
Tyco Electronics Corporation