LIMITATIONS AND EXCLUSIONS
This limited warranty shall not cover the UPS, UPS part, or BATTERY during their
respective warranty periods, if the following storage, maintenance, installation,
operating conditions are not met throughout the warranty periods (5 conditions
below):
VALVE REGUALATED LEAD ACID (VRLA) BATTERIES FOR TOSHIBA
INTERNATIONAL CORPORATION UPSREQUIRED OPERATING
1.
Temperature
2.
Maximum number
of full charge/discharge
cycles
VALVE REGUALATED LEAD ACID (VRLA) BATTERIES FOT TOSHIBA
INTERNATIONAL CORPORATION UPS
INSTALLATION AND MAINTENANCE CONDITIONS
3.
Storage
4.
External Batteries
5.
Idle Batteries
CONDITIONS
Annual
Average
Temperature per cell < 32°C
Temperature
25°C
(89°F) for more than 30
(77°F)
days
Discharge time
Maximum Number of
Cycles (24 months)
30 minutes
69
15 minutes
86
10 minutes
110
5 minutes
130
While UPS is in transit or storage it must always be in
suitable temperature (see condition 1).
Parallel battery string applications must be approved
by TIC in writing.
User must recharge the batteries if not in use
(charged) for more than 6 months.