Toshiba Compliant Manager BMS-CM1280TLE Installation Manual page 12

Compliant manager bms-cm1280tle
Table of Contents

Advertisement

Compliant Manager
<DIP-SW2>
<1> to <3> Timer input switching
These bits switch operation when the schedule timer has changed.
• Use (1) and (2) only in the remote control mode.
• When the control group selection is used, "All ON," "All OFF" and
"all indoor units" mean those within the set group range.
Central controller operation
Timer OFF → ON
(1)
All ON
(2)
No change
Individual control of all indoor
(3)
units to be permitted
(4)
Ditto
(5)
Ditto
(6)
Ditto
<4> Always OFF
Always set this bit to OFF.
<5> Control group Selection line
OFF: LINE 1
ON: LINE 2
* Set a line number for which the control group selection is used.
<6> Control group selection enable
OFF: Normal mode
ON: Control group selection
Set this bit to ON when the control group selection is used.
* To use the control group selection, set SW1-<2> to <5> and SW2-<5> to
<6>. For details, see the table on the previous page.
<7> Buzzer
OFF: With buzzer sound
ON: Without buzzer sound
<8>
indication
OFF: Displayed
ON: Not displayed
11-EN
Switch No.
Timer ON → OFF
All OFF
All OFF
All indoor units CENTRAL 1
All OFF and all indoor units to
be CENTRAL 1
All indoor units CENTRAL 2
All OFF and all indoor units to
be CENTRAL 2
– 12 –
Factory setting: All OFF
DIP-SW2
1
2 3 4 5 6 7 8
ON
OFF
#1
#2
#3
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON