Monitoring And Controlling Items Of A/C - LG BNU-BAC Installation & Owner's Manual

Bacnet gateway
Hide thumbs Also See for BNU-BAC:
Table of Contents

Advertisement

Available languages

Available languages

Monitoring and Controlling Items of A/C

The items to monitor and control A/C from BACnet communication as well as descriptions of each
item are listed below.
Function
ON/OFF (status)
Operation Mode (status)
Lock (status)
Fan speed (status)
Swing (status)
User Mode (status)
Room Temperature
Filter Sign
Alarm
Error Code
ON/OFF (setting)
Operation Mode (setting)
User Mode (setting)
Swing (setting)
Fan Speed (setting)
Lock (setting)
Set Room Temperature
Filter Sign Reset
Functional Specifications BACnet Gateway
Monitors ON/OFF status of each A/C.
Monitors cooling, heating, and vent operation status.
Indicates whether LOCK function of the A/C is active.
Monitors Fan speed of the functioning A/C.
Monitors swing mode of the indoor units.
Monitors the operation status of user mode (Quickoperation/Power
saving /Heater) while vent is functioning.
Monitors the room temperature and indicates the actual room
temperature.
Monitors the status of the filters for vent
Monitors whether the A/C are operating properly and if not, alarm is
set off.
Indicates the respective code for the errors occurred from the A/C
system or the network.
Starts and stops the respective A/C and monitors control results.
Sets the operation mode (cooling, heating, vent or auto mode) and
monitors the setting results.
Sets the additional operation mode in vent (quick fresh, energy
efficiency, heating)
Sets the air direction of the indoor unit.
Sets the airflow of the A/C
Sets the lock of the A/C's control authority.
Sets room temperature of the respective A/C and monitors the setting
results.
Resets the ventilation's filter limit indication.
Description