FOR SERVICE PERSONNEL ONLY
SPLIT UNIT AIR CONDITIONER

INSTALLATION MANUAL

Indoor Unit
Outdoor Unit
RAS-70YHA1
RAC-70YHA1
RAS-80YHA1
RAC-80YHA1

SAFETY PRECAUTION

G
Read the safety precautions carefully before operating the unit.
G
The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
WARNING ........ Incorrect methods of installation may cause death or serious injury.
!
CAUTION ......... Improper installation may result in serious consequence.
!
Be sure that the unit operates in proper condition after installation. Explain to customer the proper way of operating
the unit as described in the user's guide.
!
G
Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may occur if you
do the installation work yourself.
G
Please observe the instructions stated in the installation manual during the process of installation. Improper installation may
cause water leakage, electric shock and fire.
G
Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the
units may collapse and impose danger.
G
Observe the rules and regulations of the electrical installation and the methods described in the installation manual when
dealing with the electrical work. Use power cables approved by the authorities of your country.
G
Be sure to use the specified wire for connecting the indoor and outdoor units. Please ensure that the connections are tight
after the conductors of the wire are inserted into the terminals. Improper insertion and loose contact may cause over-heating
and fire.
G
Please use the specified components for installation work. Otherwise, the units may collapse or water leakage, electric shock
and fire may occur.
G
Be sure to use the specified piping set for R410A. Otherwise, this may result in broken copper pipes or faults.
G
When installing or removing an air conditioner, do not allow air or moisture to remain in the refrigeration cycle. Otherwise,
pressure in the refrigeration cycle may become abnormally high so that a rupture may be caused.
G
Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fire, a poisonous
gas may occur.
G
After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks
into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
G
Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner
technician or electrician. Improper repairs may result in water leakage, electric shock and fire, etc.
!
G
A circuit breaker or fuse (30A time delay) must be installed. Without a circuit breaker or fuse the danger of electric shock
exists.
A main switch with a contact gap of more than 3mm has to be installed in the power supply line to the outdoor unit.
G
Do not install the unit near a location where there is flammable gas. The outdoor unit may
catch fire if flammable gas leaks around it.
G
Please ensure smooth flow of water when installing the drain hose.
G
Piping shall be suitable supported with a maximum spacing of 1m between the supports.
1
Installation of Hanger, Wall Penetration and Installation of Protection Pipe
CAUTION
!
The draining of the water container inside the indoor unit can be done from the left.
G
Therefore the hanger must be fixed horizontally or slightly tilted towards the side of
drain hose. Otherwise, condensed water may overflow the water container.
Direct Mounting On The Wall
Please use hidden beams in the wall to hold the hanger.
G
External dimension of
indoor unit
141mm
10mm
93mm
141mm
Drain Hose
58mm
1150mm
Hanger
Screw for Hanger
Please use more
than 5 screws.
Procedures of Installation and Precautions
Procedures to fix the hanger.
G
1. Drill holes on wall.
2. Push plug into the holes.
(As shown below)
(As shown below)
G
Procedures to fix the holder of remote control.
1. Drill holes on wall.
2. Push plug into the holes.
(As shown below)
(As shown below)
Wall Penetration and Installation of Protection Pipe
G
Drill a ø 80mm hole on
wall which is slightly tilted
Indoor
Outdoor
towards the outdoor side.
Seal with
Drill the wall at a small
putty
Seal with
angle.
putty
G
Cut the protection pipe
according to the wall
thickness.
G
Empty gap in the sleeve
of protection pipe should
WALL
Protection
be completely sealed
pipe
with putty to avoid
Sleeve of
protection
dripping of rain water into
pipe
the room.
<
>
IA77: A
G
Carefully read through the procedures of proper
installation before starting installation work.
G
The sales agent should inform customers regarding
the correct operation of installation.
Tools Needed For Installation Work
G
+ – Screwdriver
G
Measuring Tape
G
Saw
G
ø 65mm Power Drill
G
Allen Key (
G
Wrench (14, 17, 19, 22mm)
G
Gas Leakage Detector
G
Pipe Cutter
G
Plastic Tape
G
Pliers
G
Flare Tool
WARNING
CAUTION
2
Installation of the Indoor Unit
DIRECTLY BACKWARD AND DOWNWARD PIPING
Preparation
Connect connecting cord.
G
Pull out the pipe, connecting cord and drain hose.
G
G
Arrange a drain hose in lowest part of a wall hole.
Installation
The upper part of the Indoor unit is hanged on the hanger.
G
The projection at the lower part of the Indoor unit is hooked onto the hanger.
G
Hanger
Level
Protection
Pipe
Drain Hose
Line
Mark
Hole for
Weight
pipe
HOW TO REMOVE INDOOR UNIT FROM HANGER
Push up PUSH section on the bottom of indoor
G
unit, then claws are released from hanger.
(Indicated by 2 arrows in the drawing on the
right.)
3. Fix the hanger on wall
with 4.1 x 32 screw
HORIZONTAL PIPING
(As shown in figure below)
Preparation
Change of Drain Hose and Installation Procedures.
G
Exchange the location of drain hose and drain cap during horizontal piping as shown in
figure below. Be sure to plug in the drain hose until the insulating material folds upon itself.
G
Please use pliers to pull out the drain cap.
(This is an easier way to remove the drain cap).
Please insert
until here
WARNING
!
CAUTION
!
2 ~ 5mm
Be sure that the wire is not
in contact with any metal
HORIZONTAL & DOWNWARD PIPING – MAKING OPENINGS
in the wall. Please use the
During horizontal or downward piping, use a knife to cut
G
protection pipe as wire
passing through the hollow
openings as shown in figure. Then smoothen the edges of
part of the wall so as to
openings with a file.
prevent the possibility of
Pipe
damaged by mouse.
support
Unless it seals completely,
any air with high humidity
flows from outdoor and
any dew may drop.
THE CHOICE OF MOUNTING SITE
G
The unit should be mounted at stable, non-vibratory location which
can provide full support to the unit.
G
No nearby heat source and no obstruction near the air outlet is
allowed.
G
The clearance distances from top, right and left are specified in
figure below.
G
Knife
G
The location must be convenient for water drainage and pipe
4mm)
connection with the Outdoor unit.
G
To avoid interference from noise please place the unit and its
remote controller at least 1m from the radio, television and inverter
type fluorescent lamp.
G
To avoid any error in signal transmission from the remote controller,
please put the controller far away from high-frequency machines
and high-power wireless systems.
G
The installation height of indoor unit must be 2.3m or more.
Names of Indoor Components
No.
Component's Name
Hanger
1
Screw for Mounting Plate
2
( 4 . 1 x 3 2 )
Holder for Remote
Controller
3
AAA Size Battery
4
Screw for holder of
Remote Controller
5
( 3 . 1 x 1 6 )
Insulation pipe
6
Remote Controller
7
Purifying Filter
8
Names of Outdoor Components
No.
Item
Bush
8
Bush
9
Drain Pipe
10
Connecting cords,
pipe and drain hose
must be tied together
with Vinyl tape.
Pipe
small
Pipe
dia.
large
Cable
dia.
Wall hole
Drain hose
Hanger
1
!
CAUTION
Lift the body
Please pull the lower part of
Refrigerating
of the unit
Pipe
the Indoor unit outwards to
upwards and
then force it
check if the unit is hooked
downwards.
onto the hanger. Improper
2
installation
Connecting
vibration and noise.
Projection
Cord
Drain cap
Drain hose
Drain cap
Drain hose
Please insert
until here
Condensed water may leak out if not inserted properly.
G
Turn the piping while holding down the lower
Pull up the pipe after
portion of pipe-support by hand.
bending downward
(Please note the following matters and obtain permission from customer before installation).
WARNING
!
G
The Outdoor unit must be mounted at a location which can sup-
port heavy weight. Otherwise, noise and vibration will increase.
!
CAUTION
G
Do not expose the unit under direct sunshine or rain. Besides, ventilation
must be good and clear of obstruction.
G
The air blown out of the unit should not point directly to animals or plants.
G
The clearances of the unit from top, left, right and front are specified in
figure below. At least 3 of the above sides must be open air.
G
Be sure that the hot air blown out of the unit and noise do not disturb the
neighbourhood.
G
Do not install at a location where there is flammable gas, steam, oil and
smoke.
G
The location must be convenient for water drainage.
G
Place the Outdoor unit and its connecting cord at least 1m away from the
antenna or signal line of television, radio or telephone. This is to avoid
noise interference.
G
Do not install outdoor unit facing strong wind direction. It may damage the
fan motor.
The Length of Indoor Unit
Figure showing the Installation of Indoor and
Connecting Cord
Qty
Outdoor Unit.
0.9m
1.6m
!
CAUTION
1
In case the pipe length is more than 20m, add refrigerant R410A
at 15 gram per every meter exceeds. However, pipe length shall
not exceed 30m.
6
Cut away shaded
portion, and finish
the edge of the
opening so that
20
there is no burr.
1
Be sure to
Direction of Piping
completely
seal any
gap with
putty.
2
Horizontally
perpendicular
to the unit
Connection
2
There
are
6
directions
allowed, namely, horizontally
perpendicular to the unit,
vertically down from right,
horizontally out from right and
1
horizontally out to left.
Dimension of Mounting Stand
of the Outdoor unit
1
(unit : mm)
mounting stand
57
1
12
35
508
198
Qty
1
3
500
1
INSTALLATION OF REFRIGERATING PIPES AFTER CONNECTION
The refrigerating pipes should be adjusted to fit into
G
the hole on the wall and then ready for further
connection.
G
The terminals of 2 connected pipes must be covered
with insulator used for terminal connection. Then the
pipes are wrapped with insulation pipe.
Connect the connecting cord after removing electrical
G
cover. (Refer to "CONNECTION OF POWER CORD")
G
After adjustment, fit the connecting cord and pipes
into the space available under the indoor unit. Use
holder to hold them tight.
Pipe
large
dia.
Pipe
small dia. Cable
Holder
Layout of pipe
Insulation pipe (must be wrapped with
6
vinyl tape at every 120mm).
G
Holder can be attached at the either of 2 places.
Please select the easier position.
THE CONNECTION OF REFRIGERATING PIPE DURING THE
may
cause
INSTALLATION OF INDOOR UNIT
Preparation To Install Refrigerating Pipes
The refrigerating pipes and connecting cord
G
transform and are attached.
G
The end of the refrigerating pipes are at locations
marked with "
" symbol.
Please expand
the pipes and
match the
1.0m
Installation
Hang the Indoor unit onto the hanger. Use the temporary stand
at the back of the Indoor unit to push its lower part 15cm
forwards.
Place the drain hose through the hole on the wall.
G
Wrap the refrigerating pipes with insulation pipe after
G
connecting refrigerating pipe.
G
Connect the connecting cord after removing electrical cover.
(Refer to "Connection of Power Cord")
After adjustment, the connecting cord and refrigerating pipes
G
are placed into the space available under the Indoor unit.
Use holder to hold them tight.
G
The projection of Indoor unit must hook to the hanger.
Heat insulation pipe
Pull this to the front
during the connection
of refrigerating pipes
Connecting
to ease task.
cord
Refrigerating pipe
3
Installation of Drain Hose
Openings
Bending
Condensed
upwards
water pond
You are free to choose the side (left or right) for the installation of drain
!
hose. Please ensure the smooth flow of condensed water of the Indoor
CAUTION
unit during installation. (Carelessness may result in water leakage.)
WARNING
!
CAUTION
!
2
above 50mm
1
above
above 100mm
200 mm
above 2300 mm
7
The indoor piping should be
insulated with the enclosed
insulation pipe. (If the
insulator is insufficient,
please use commersial
products).
G
The difference in height
between the indoor and
outdoor unit should be
kept max 10m.
G
The connecting pipe, no
matter big or small,
should all be insulated
with insulation pipe and
then wrapped with vinyl
tape. (The insulator will
deteriorate if it is not
wrapped with tape).
The connection of insulated
drain hose.
inner diameter ø 16mm
Please use insulated drain
hose for the indoor piping
(commercial product).
Drain hose
Pipe
Connecting cord
!
CAUTION
Pipe
Pipe
small
large
G
The rubber strap used for
dia.
dia.
fixing the insulator should
Cable
not be tied with great force.
Otherwise, this will damage
Drain hose
heat insulation and causes
Layout of pipe
water condensation.
Pipe
Rubber strap tied with great force
!
CAUTION
Please fix in the plastic core
G
after flaring to avoid plastic
chips entering the pipes.
below
symbol
5mm
Please bend at a small
radius to form an arc
Temporary stand
Projection
Hook
about 15cm
Protection pipe
Drain hose
Connecting cord
Holder Connected section
CAUTION
!
Be sure that the
drain hose is not
loosely connected
Condensed
Ditch
water pond
or bend.

Advertisement

loading

Summary of Contents for Hitachi RAC-70YHA1

  • Page 1: Installation Manual

    Wrench (14, 17, 19, 22mm) To avoid interference from noise please place the unit and its Do not install at a location where there is flammable gas, steam, oil and RAS-70YHA1 RAC-70YHA1 smoke. Gas Leakage Detector Pipe Cutter remote controller at least 1m from the radio, television and inverter The location must be convenient for water drainage.
  • Page 2 Preparation of Pipe Removal Of Air From The Pipe And Gas Leakage Inspection Please face this side Please mount the outdoor unit on (suction side) of the stable ground to prevent vibration unit to the wall. Use a pipe cutter to cut the copper pipe. and increase of noise level.

This manual is also suitable for:

Ras-70yha1Ras-80yha1Rac-80yha1