Mitsubishi Electric PURY-P200 Service Handbook page 180

City multi r410a
Table of Contents

Advertisement

Check whether the BC board output signal and the solenoid valve operation correspond.
Note1 SVA, SVB, SVC
SVA, SVB and SVC turn on or off according to the indoor unit operation mode.
Mode
Branch end
SVA
SVB
SVC
SVM1, SVM2 [P400-P550 types]
SVM1,SVM2 turns on or off according to the operation mode.
Operation mode
Cooling-only
SVM1
SVM2
Note2 SVA, SVB, SVC
Measure the temperature of the piping 1-2 which is in front and behind the SVA.
Measure the temperature of the piping 1-3 which is in front and behind the SVB.
3
2
1
(4) BC controller transformer
BC controller control board
CNTR
Red
White
Cooling
ON
OFF
ON
Cooling-main
Pressure difference
ON
control OFF or ON
OFF
OFF
CN03
Red
Red
Heating
OFF
ON
OFF
Heating-only
Heating-main
OFF
OFF
Pressure difference
Pressure difference
control OFF or ON
control OFF or ON
Normal
CNTR(1)-(3)
about 58Ω
CN03(1)-(3)
about 1.6Ω
✻ Before measuring the resistance, pull out the connector.
- 177 -
Stop
Defrost
OFF
OFF
OFF
OFF
OFF
OFF
Defrost
ON
OFF
Abnormal
Open-phase
or shorting
Stop
OFF
OFF