(6) Solenoid valve
Work procedure
1. Remove the service panel.
(Refer to (1)-1.2.3.)
2. Remove the connector of the applied solenoid valve.
3. Remove the solenoid valve coil.
1 For the solenoid valve coil of SVA, SVB and SVM1, 2
service from the inspection door is possible. For SVC,
however, remove the rear panel (4 machine screws)
to replace the coil, if enough service space is secured
at the rear. (Only GA type for SVM1 and 2)
✻Special care must be taken when replacing heavy parts.
Solenoid valve
- 195 -
Explanatory figure
Double pipe heat exchanger
CMB-1016V-G
CMB-1016V-GA