Pioneer LISAS-B-1403 Service Manual page 117

Dc inverter split heat pumps
Table of Contents

Advertisement

1.3.9 Drain pump control (For cassette)
Adopt the water-level switch to control the action of drain pump.
Main action under different condition :( every 5 seconds the system will check the water level one time)
1. When the A/C operates with cooling (including auto cooling), dehumidifying, and forced cooling mode, the
pump will start running immediately and continuously, till stop cooling.
2. Once the water level increase and up to the control point, LED will alarm and the drain pump open and
continue checking the water level. If the water level fall down and LED disalarmed (drain pump delay close 1
minute) and operate with the last mode. Otherwise the entire system stop operating ( including the pump)
and LED remain alarming after 3 minutes,
1.3.10 Point Check Function (Excluding 12K &18K)
There is a check switch in outdoor PCB.
Press the switch SW1 to check the states of unit when the unit is running.
Press the switch N times it will display the content corresponding to No. N. After getting into the check
function, it will display No. N with 1.5s, meanwhile the low bit decimal of digit display flashing, indicated to
get into the check function display. After 1.5s, it will display the content corresponding to No. N.
the digital display tube will display the follow procedure when push SW1 each time.
N
00
Normal display
01
Indoor unit capacity demand code
02
Amendatory capacity demand code
The frequency after the capacity requirement
03
transfer
04
The frequency after the frequency limit
05
The frequency of sending to 341
Indoor unit evaporator outlet temp.(Cooling:T2,
06
heating:T2B)
07
Condenser pipe temp.(T3)
08
Outdoor ambient temp.(T4)
09
Compressor discharge temp.(Tp)
10
AD value of current
11
AD value of voltage
12
Indoor unit running mode code
13
Outdoor unit running mode code
14
EXV open angle
Electrical Control System
Display
Remark
Display running frequency, running state or malfunction code
Norm code *HP*10
If capacity demand code is higher than 99, the digital display
tube will show single digit and tens digit. (For example, the
digital display tube show "5.0",it means the capacity demand
is 15. the digital display tube show "60",it means the capacity
demand is 6.0)
If the temp. is lower than 0 degree, the digital display tube will
show "0".If the temp. is higher than 70 degree, the digital
display tube will show "70".
If the temp. is lower than -9 degree, the digital display tube will
show "-9".If the temp. is higher than 70 degree, the digital
display tube will show "70". If the indoor unit is not connected,
the digital display tube will show: "――"
The display value is between 13~129 degree. If the temp. is
lower than 13 degree, the digital display tube will show "13".If
the temp. is higher than 99 degree, the digital display tube will
show single digit and tens digit. (For example, the digital
display tube show "0.5",it means the compressor discharge
temp. is 105 degree. the digital display tube show "1.6",it
means the compressor discharge temp. is 116 degree)
The display value is hex number.
Off:0, Fan only 1,Cooling:2, Heating:3
Off:0, Fan only 1,Cooling:2, Heating:3, Forced cooling:4
Actual data/4.
If the value is higher than 99, the digital display tube will show
single digit and tens digit.
Electrical Control Function
115