2.4.1.5. Indoor fan Speed has been out of control. (Only for the units used DC motor)
DC motor voltage input and output (control chip is inside the motor)
DC motor voltage input and output
NO.
Color
1
Red
2
---
3
Black
4
White
5
Yellow
6
Blue
Electrical Control System
Signal
Voltage
Vs/Vm
280V~380V
---
---
GND
0V
Vcc
14-17.5V
Vsp
0~5.6V
FG
14-17.5V
Troubleshooting