Determining When To Replace Batteries; Obtaining New Batteries - HP T2200 XR User Manual

Uninterruptible power system
Hide thumbs Also See for T2200 XR:
Table of Contents

Advertisement

Battery Maintenance

Determining When to Replace Batteries

When the Bad Battery/Low Battery LED (1) illuminates red, batteries may need to be
replaced within 30 to 60 days.
Figure 4-1: Bad Battery/Low Battery LED
To check a battery alarm, initiate a UPS battery self-test to verify that battery replacement is
required. If the Bad Battery/Low Battery LED (1) remains red, replace the batteries as soon
as possible.
NOTE: Depending on usage and environmental conditions, the batteries should last three to six years.
For more information on initiating a self-test, refer to the section, "Initiating a Self-Test," in
Chapter 2.

Obtaining New Batteries

New batteries may be required within 30 to 60 days when the Bad Battery/Low Battery LED
illuminates red. Obtain spare batteries for the UPS when this occurs.
HP supplies spare battery packs for this UPS. The UPS spare battery kit part number is
240796-001
CAUTION: Because of the short shelf life of the battery, avoid storing a battery spare as a
backup. Do not maintain an onsite inventory of spare batteries unless a procedure to keep the
stored batteries charged is implemented.
4-2
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
1
.
HP Uninterruptible Power System T2200 XR Models User Guide

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

T2200 xr seriesT2200 xr naT2200 xr jpnT2200 xr h naT2200 xr h int'l204451-001 ... Show all

Table of Contents