1-2-3 Automatic address setting for signal amplifiers
When setting the address of the signal amplifier, please use the factory setting. (See the
installation manual of the signal amplifier)
When the system is normal, nothing will be displayed on the 7 segment display.
When ERROR is displayed, inspect the units.
Use the "MODE/EXIT", "SELECT", and "ENTER" buttons on the outdoor unit Main PCB
to conÞ gure settings according to the procedures below.
First 2 digits Last 2 digits
End
SWITCH POSITION
Outdoor unit printed circuit board
1: FUNCTION Setting
(the display when the main power is turned on)
MODE/EXIT
SELECT
SELECT
(When [F4] to [F9] are displayed, continue to press the "SELECT" button
until [ F3 ] is displayed)
ENTER
Automatic address setting for
signal ampliÞ ers
Press the "SELECT" button until "10" is displayed
SELECT
Press the "ENTER" button for more than 3 seconds
ENTER
*
* Setting is complete when the number of unit is displayed
ENTER
MODE/EXIT
01-06
When using signal amplifiers
POWER
ERROR
MODE
7 Segment
LED101
LED102
LED Lamp
(GREEN)
(RED)
LED105
LED104
MODE
SELECT
ENTER
Push button switch
/EXIT
SW107
SW108
SW109

Hide quick links: