Check Point : ARXB07LALH (Compact Duct Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
140°C
Pr
Check Point : ARXB09LALH (Compact Duct Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
140°C
Pr
Check Point : ARXB12LALH (Compact Duct Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
140°C
Pr
BLUE (S-Lo)
VIOLET (Low)
PINK (Med)
RED (Hi)
BLACK
(AC)
WHITE
BLUE (S-Lo)
VIOLET (Low)
PINK (Med)
RED (Hi)
(AC)
BLACK
WHITE
BLUE (S-Lo)
VIOLET (Low)
PINK (Med)
RED (Hi)
BLACK
(AC)
WHITE
04-99
Lead wire
Resistance value
White Red
579
255
Red
Black
162
Red
Pink
Pink
Violet
66
Violet
Blue
93
Lead wire
Resistance value
White Red
322.8
255
Red
Black
Red
Pink
103
Pink
Violet
53
Violet
Blue
100.7
Lead wire
Resistance value
White Red
336
261
Red
Black
107
Red
Pink
Pink
Violet
55
Violet
Blue
103
8%
8%
8%
8%
8%
at 20°C
8%
8%
8%
8%
8%
at 20°C
8%
8%
8%
8%
8%
at 20°C