22 | Installation instructions
Water conductivity for sacrificial anodes
130 S/cm - 1500 S/cm
Table 4
Water conductivity
Enamelled tanks must not be used with
completely desalted, distilled or de-ionised
potable water.
4.9
Installation checklist
1. Tank location
•
Is the room size less than 3 m x 3 m x 2,5 m (22,5 m
If yes, louvered door or similar ventilation is needed with
2
minimum 500cm
venting area.
•
Clearances according to figure 7 (section 3.7, page 14).
•
Front of unit is free and clear.
•
Is the water heater leveled? If not, adjust the adjustable
feet, or add shims under the base of the unit.
•
Are fixing straps (if required) in place?
2. Plumbing connections
•
No leaks after filling the tank with water, either when water
is flowing or is stationary.
3. Condensate lines are in place
•
Condensate drain pipe connected to drain connection, and
directed into a floor drain or a condensate pump
4. Temperature and pressure-relief valve is working and
drain line completed per local code.
5. Electrical connections
•
Electrical connections are properly isolated
6. Water filling and purge procedure
•
Water filling and purge procedure done according to
section 4.8.
7. Sensors location
•
Are the sensors at their correct place (Fig. 16, [A - fins
temperature], [B - top tank temperature], [C - air
temperature] and [D - bottom tank temperature])?
If not:
▶ Locate the sensors according to Fig. 16.
6 720 808 869 (2014/06)
8. Verify control panel displays the water temperature
inside the tank.
9. Top cover in place.
WARNING:
The power supply to the appliance must not
be activated until the system is filled with
water.
3
)?
Fig. 16
Sensor positioning
6720807918-07.2V