[ VIII Test Run Mode ]
Model name of BC controller
Ambient
tempera-
ture
Indoor unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
ing
BC controller (1/2/3)
High pressure(63HS1)/
Low pressure(63LS)
Pressure
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
Outdoor
unit
Temp. of
each sec-
tion
Indoor unit
HWE0803A
Operation
Indoor
DB/WB
Outdoor
No. of connected units
No. of units in operation
Model
Main pipe
Branch pipe
Total pipe length
[lbs-oz]
Pulse
Discharge (TH4)
Heat exchanger outlet
(TH3)
Accumulator inlet
Accumulator outlet
Compressor inlet
Compressor shell bottom
LEV inlet
Heat exchanger inlet
- 164 -
Outdoor unit model
PURY-P120THMU-A
CMB-P104NU-G
26.7°C/19.4°C
[80°F/67°F]
35°C/-
[95°F/-]
4
Unit
4
-
30/30/30/30
5 [16-3/8"]
m
10 [32-3/4"]
[ft]
45 [147-5/8"]
-
Hi
kg
22.5 [50]
A
29.5
V
230
Hz
75
230/230/230/230
2000/-/210
2.82/0.89
[409/129]
MPa
[psi]
2.73/2.72
[395/394]
82 [180]
43 [109]
8 [46]
°C
8 [46]
[°F]
20 [68]
42 [108]
22 [72]
11 [52]
GB