[ VIII Test Run Mode ]
Model name of BC controller
Ambient
tempera-
ture
Indoor unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
ing
BC controller (1/2/3)
High pressure(63HS1)/
Low pressure(63LS)
Pressure
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
Outdoor
unit
Temp. of
each sec-
tion
Indoor unit
HWE0803A
Operation
Indoor
DB/WB
Outdoor
No. of connected units
No. of units in operation
Model
Main pipe
Branch pipe
Total pipe length
[lbs-oz]
Pulse
Discharge (TH4)
Heat exchanger outlet
(TH6)
Accumulator inlet
Accumulator outlet
Compressor inlet
Compressor shell bottom
LEV inlet
Heat exchanger inlet
- 174 -
Outdoor unit model
PURY-P192TSHMU-A
PURY-P96THMU-A
CMB-P108NU-GA
21.1°C/- [70°F/-]
8.3°C/6.1°C [47°F/43°F]
Unit
-
30/30/30/30/36/36
m
[ft]
-
kg
A
V
Hz
71
295/295/295/295/350/350
110/110/1050
2.67/0.68
[387/98]
MPa
[psi]
80 [176]
0 [32]
-2 [28]
°C
-3 [27]
[°F]
-3 [27]
40 [104]
PURY-P96THMU-A
6
6
5 [16-3/18"]
10 [32-3/4"]
65 [213-1/4"]
Hi
42.4 [93]
44.2
230
71
2.79/0.58
[405/81]
2.63/2.31
[381/335]
80 [176]
0 [32]
-2 [28]
-3 [27]
-3 [27]
40 [104]
38 [100]
70 [158]
GB