Product Information MAGIC.SENS -- Product range
11.5. Test procedure for MAGIC.SENS OC 310 GLT
With the OC 310 you must first test the optical unit with the test aerosol. After triggering
the O unit, the detector must be reset. Thus the CO sensor is switched into
maintenance mode for 15 minutes and it can then be tested. Since the aerosol test for
the detectors works like a disturbance signal, (very large signal with very quick
increase), the signal evaluation for disturbance variable is brought to bear and the
alarm occurs only after approximately one minute.
D Position detector testers for smoke detectors on the OC 310 GLT.
D Spray aerosol (1 to 2 seconds).
. Do not remove test device from the detector; the O unit triggers only
approximately 60 seconds after the application of the test aerosol.
D Reset detector.
. Thus the detector is switched into maintenance mode.
D Place CO gas bottle in the test device.
D Position test device on the detector.
D Apply CO gas for
. The C sensor triggers after approximately 20 seconds.
11.6. Inspection procedure for OT 300 GLT / O 300 GLT
D Position detector testers for smoke detectors on the OT 300 GLT / O 300 GLT.
D Spray aerosol (1 to 2 seconds).
. Do not remove test device from the detector; the O unit triggers only
approximately 30 seconds after the application of the test aerosol.
D Reset detector.
. Thus the detector is switched into maintenance mode.
D The temperature sensor of the OT is tested with the test device for heat detectors.
1
/
to 1 second.