 Wire connection
REQUIREMENT
• Connect the wires matching the terminal numbers. Incorrect connection causes a trouble.
• Pass the wires through the bushing of wire connection holes of the hot water module.
• Keep a margin (Approx. 100 mm) on a wire to hang down the electrical control box at servicing or other purpose.
• The low-voltage circuit is provided for the remote controller. (Do not connect the high-voltage circuit)
• Remove the front panel of the hot water module by taking off the mounting screws (2 positions).
• Tighten the screws of the terminal block, and fix the wires with cord clamp attached to the electrical control box.
(Do not apply tension to the connecting section of the terminal block.)
• Mount the front panel of the hot water module without pinching wires.
Front
panel
R
S
(L)
(N)
COM S1 S2 S3 S4 S5
U1 U2 A B
43-EN
Power supply wiring port
Control wiring port
External signal wiring port
R
S
(L)
(N)
Earth wire
Power supply wire
Side D (Space: 8.5 mm)
Side C (Space: 4 mm)
Earth Screw
Cord clamp
(For power supply
wire)
* Cable clamp can be attached on left side.
Wire
Specification
type
Cabtyre
3-core stranded
Power supply wire
cable
wire 2.5 mm²
Cabtyre
4-core stranded
Remote controller wire
cable
wire 1.5 mm²
Control wire
Output signal function wire
 Remote controller wiring
• Strip off approx. 9 mm the wire to be connected.
▼ Wiring diagram
 Output signal function wiring
Connect the following output signals from the hot water module.
Terminal
block No.
COM
DC12V (COM)
S1
Defrosting output (COM-S1)
S2
Line heater output (COM-S2)
(Unit: mm)
S3
S4
Heating thermostat ON output (COM-S4)
S5
Pump output (COM-S5)
Hot water module
output signal
function terminal
block (CN60)
NOTE
Auxiliary relays (locally procured) must be connected to output signal function wirings to allow connection to the
Cable clamping
position
hot water module output signal functions. The maximum current output signal, from each of the output signal
function wirings, is 16 mA. Please ensure the rated current of the relay coil is less than 16 mA to avoid damage to
Side D
the hot water module P.C. board.
Side C
– 22 –
Terminal block for
remote controller wiring
Terminal block
of hot water module
A
A
Remote controller unit
B
B
Remote controller wire
(Locally procured)
Function
Common for connector S2 ~ S5
DC12V
Relay coil is less than 16mA.
DC12V
Relay coil is less than 16mA.
-
DC12V
Relay coil is less than 16mA.
DC12V
Relay coil is less than 16mA.
Relay
COM
S1
S2
Output function wire
S3
S4
S5
Locally procured
Comments
-
External
actuator
44-EN