Lenovo System x PDU Technical Reference page 70

Table of Contents

Advertisement

.
Specifications
The following table are specifications for 71762NX DPI Ultra Density Enterprise PDU.
Specifications Line cord PN Line cord PN Line cord PN Line cord PN Line cord PN
Input Line
40K9611
Cord Type*
Type
32A/380-
415V
Phase
Three
Outlets types nine IEC
C19,
three IEC
C13
Power
22080VA @
Capacity**
230V
Power Limit
IEC C19:
per Outlet
16A
IEC C13:
10A
Grouping
One C19 +
one C13 or
One C19
outlet per
breaker /
Three C19 +
one C13
outlets per
phase
Power Limit
20A per
per Group
breaker /
32A per
phase
Power Limit
96A
per PDU
Monitoring/
No/No
Switching
U Space
1U or side pocket
Grounding
Yes on back panel
Screw
* For input line cord part numbers refer to the
** For the purpose of this table, you can consider 1VA = 1 Watt.
70
40K9612
40K9613
32A / 220-
63A/220V-
240V
240V
Single
Single
nine IEC
nine IEC
C19,
C19,
three IEC
three IEC
C13
C13
7360VA @
14490VA @
230V
230V
IEC C19:
IEC C19:
16A
16A
IEC C13:
IEC C13:
10A
10A
One C19 +
One C19 +
one C13 or
one C13 or
One C19
One C19
outlet per
outlet per
breaker
breaker
20A
20A
32A
63A
Input Line Cords
40K9617
40K9618
32A / 230V
30A / 230V
Single
Single
nine IEC
nine IEC C19,
C19,
three IEC
three IEC
C13
C13
7360VA @
6600VA @
230V
220V
IEC C19:
IEC C19: 16A
16A
IEC C13: 10A
IEC C13:
10A
One C19 +
One C19 +
one C13 or
one C13 or
One C19
One C19
outlet per
outlet per
breaker
breaker
20A
20A
32A
30A
section.

Advertisement

Table of Contents
loading

Table of Contents