Mitsubishi Electric 9700 Series Owner Technical Manual page 59

Mitsubishi uninterruptible power system technical manual
Hide thumbs Also See for 9700 Series:
Table of Contents

Advertisement

MITSUBISHI
ELECTRIC
Fault Code List
Note 11.
Code
Status massage
indication
UF003
CONVERTER ABNORMAL Preliminary charge impossible
UF007
SENSOR ABNORMAL
UF052
CB1 TRIPPED
UF053
CB1 ABNORMAL
UF056
CONVERTER OVERLOAD Converter input overcurrent
CONVERTER
UF057
OVERTEMPERATURE
COOLING FAN
UF058
ABNORMAL
UF059
CONVERTER ABNORMAL Converter control circuit abnormality
UF102
DC OVERVOLTAGE
UF103
DC UNDERVOLTAGE
UF105
SENSOR ABNORMAL
DC CAPACITANCE
UF106
ABNORMAL
UF107
CB2 ABNORMAL
UF151
DC VOLTAGE ABNORMAL
UF152
DC VOLTAGE ABNORMAL
UF153
CB2 TRIPPED
CB2 TRIPPED (BATTERY
UF156
OVERTEMPERATURE)
BATTERY
UF157
OVERTEMPERATURE
UF158
BATTERY LIQUID LEVEL
(Note10)
LOW
UF159
DC GROUND FAULT
UF160
SENSOR ABNORMAL
CB2 TRIPPED (DC
UF161
VOLTAGE ABNORMAL)
UF162
BATTERY ABNORMAL
INVERTER
UF201
OVERVOLTAGE
INVERTER
UF202
UNDERVOLTAGE
INVERTER
UF203
OVERCURRENT
UF209
52C ABNORMAL
UF210
52C ABNORMAL
UF212
FAN ABNORMAL
INVERTER OR
UF213
CONVERTER
OVERTEMPERATURE
COOLING FAN
UF214
ABNORMAL
UF215
FREQUENT OVERLOAD!
UF216
SENSOR ABNORMAL
9700 SERIES UPS
OWNERS / TECHNICAL MANUAL
Contents
Converter
input
current
sensor
abnormality
Input circuit breaker CB1 has tripped
Input circuit breaker CB1 abnormal
Overheating of converter circuit parts
Abnormality of cooling fan (converter circuit)
Overvoltage of DC voltage
Low voltage of DC voltage
DC voltage sensor circuit abnormality
Electrolytic capacitor abnormality
Battery
disconnect
circuit
abnormal
Does not return to float voltage after power
supply is resumed (24 hours)
Does not return to equalizing voltage after
power supply is resumed
Battery disconnect circuit breaker CB2 has
tripped.
Battery temperature abnormality (UF157) lasted
a long time (Note 6)
Battery temperature abnormality
Battery solution level drop (Note 7)
Grounding of DC circuit
Sensor abnormality of battery circuit
Does not return to float voltage after power
supply is resumed (48 hours) (Note 6)
Battery abnormal detected by battery self test.
Output overvoltage during inverter power supply
(+ 15%)
Output low voltage during inverter supply (-
15%)
Inverter output overcurrent
52C not turned ON
52C not turned OFF
Fan power source abnormality during operation
Overheating of main circuit parts
Abnormality of cooling fan inside panel
Load switching was made frequently during
overload
Inverter output current sensor abnormality
MITSUBISHI ELECTRIC 9700 SERIES UPS
Note 1
Note 2
Guidance Buzzer
1
[2]
circuit
1
[2]
1
[1]
1
[1]
1
[1]
1
[1]
1
[1]
1
[1]
1
[2]
1
[2]
1
[2]
1
[2]
breaker
CB2
1
[2]
2
[1]
2
[1]
1
[1]
1
[1]
2
[1]
2
[1]
1
[1]
1
[1]
2
[1]
1
[2]
1
[2]
1
[2]
1
[2]
1
[2]
1
[2]
1
[2]
1
[2]
4
[2]
1
[2]
Page Number:
6-2
Note 3
Note 4
External
Failure
send-out
Code No.
lamp
contact
Major
Lit up
64
Major
Lit up
1
Minor
Flicker
97
Minor
Flicker
96
Minor
Flicker
192
Minor
Flicker
194
Minor
Flicker
193
Minor
Flicker
198
Major
Lit up
5
Major
Lit up
6
Major
Lit up
2
Major
Lit up
77
Major
Lit up
66
Minor
Flicker
116
Minor
Flicker
117
Minor
Flicker
100
Minor
Flicker
107
Note 5
Minor
Flicker
106
Note 5
Minor
Flicker
105
Note 5
Minor
Flicker
112
Minor
Flicker
114
Minor
Flicker
196
Major
Lit up
12
Major
Lit up
13
Major
Lit up
26
Major
Lit up
75
Major
Lit up
76
Major
Lit up
65
Major
Lit up
69
Major
Lit up
67
Major
Lit up
86
Note5
Major
Lit up
11