3.0 INSTALLATION AND OPERATION

3.1 Transportation and Installation

TABLE 3.1 How to transport and install the system

Transportation
Transport unit with forklift.
Use eye bolts (supplied) to carry with
overhead crane.
Do not transport in a horizontal position. Cabinets should be maintained
Note :
upright within +/- 15° during handling

3.2 Installation Procedure

A) Note the load tolerance of the floor
Refer to Table 3.2 for list of weights of UPS's.
TABLE 3.2 List of UPS weights
UPS Capacity (kVA)
Weight (lb.)
B) Minimum clearance required for ventilation
Right side
Left side
Back side
Top side
C) Space requirement for routine maintenance
Allow the following space at the time of installation.
Front
Sides
Rear
9700 SERIES UPS
OWNERS / TECHNICAL MANUAL
100
150
3060
3810
1.0" (25 mm) (not required when sidecars are used)
1.0" (25 mm) (not required when sidecars are used)
0.0" (0.0 mm)
23.6" (600 mm) (for air flow)
39.4" (1000 mm)
0.0" (0.0 mm)
0.0" (0.0 mm)
MITSUBISHI ELECTRIC 9700 SERIES UPS
Installation
Using the holes (4 - 24) pre drilled into the
UPS channel base, anchor the unit using
appropriate hardware.
.
225
4960
5890
Page Number:
3-1
300
375
6620