MITSUBISHI
ELECTRIC
3.0 INSTALLATION AND OPERATION
3.1 TRANSPORTATION AND INSTALLATION
Table 3.1 How to Transport and Install the System
Transportation
Transport unit with forklift.
Carry with overhead crane using
provided screw-eyebolts.
CAUTION: Do not transport in a horizontal position. Cabinets must be
3.2 INSTALLATION PROCEDURE
A) Note the load tolerance of the floor
Refer to Table 3.2 for list of UPS weights.
UPS Capacity (kVA)
B) Minimum clearance required for ventilation:
Right side
Left side
Back side
Top side
9900B SERIES UPS
OWNERS / TECHNICAL MANUAL
Using the pre-drilled four holes in the UPS
channel base, anchor the unit using appropriate
hardware (not provided).
maintained upright within +/- 15° of the vertical during handling.
Table 3.2 List of UPS Weights
Weight (lb.)
2,250
25 mm (1 inch) (not required when sidecars are used)
25 mm (1 inch) (not required when sidecars are used)
0.0 mm (0 inch)
600 mm (24 inches) (for air flow)
MITSUBISHI ELECTRIC 9900B SERIES UPS
Installation
300
500
3,570
4,255
Page Number:
3-1
750