1/3" CMOS Ultra Wide
Dynamic Color Camera
CCWC1345-LX
CCWC1345-MX
Configuration Manual
Fire Safety & Security Products
Siemens Building Technologies

Advertisement

Table of Contents
loading

Summary of Contents for Siemens CCWC1345-LX

  • Page 1 1/3” CMOS Ultra Wide Dynamic Color Camera CCWC1345-LX CCWC1345-MX Configuration Manual Fire Safety & Security Products Siemens Building Technologies...
  • Page 2 Dear Customer By selecting this SIEMENS product, you have chosen a professional device that guarantees the highest possible quality and reliability. We would like to thank you...
  • Page 3: Table Of Contents

    D/N LEVEL....................22 6.2.3.3 D/N DELAY .....................22 6.2.4 OPTION ....................22 6.2.4.1 Mirror.......................23 6.2.4.2 DZOOM....................23 6.2.4.3 DZOOM IN OUT..................23 6.2.4.4 DZOOM P/T SET ..................23 6.2.4.5 CHROMA ....................23 6.2.4.6 COLOR BAR ...................24 6.2.4.7 DNR ......................24 Siemens Building Technologies Fire Safety & Security Products 08.2006...
  • Page 4 PROTOCOL ....................28 6.2.6.3 BAUD RATE....................28 6.2.7 PRIVACY ZONE ..................28 6.2.8 BLC ZONE ....................29 6.2.9 SYNC MODE...................30 6.2.10 BACK.......................30 6.2.11 EXIT ......................30 6.2.12 CANCEL....................30 6.2.13 DEFAULT ....................30 Maintenance...................31 Disposal ....................31 Keyword index..................32 Siemens Building Technologies Fire Safety & Security Products 08.2006...
  • Page 5: General Information

    To ensure normal operation and to avoid EMC problems, the product must be in- stalled according to the currently valid EMC installation guidelines. To meet the CE norms, enclosed EMI-cores should be applied to the Y/C and power cable (please refer to chapter 7.1). Siemens Building Technologies Fire Safety & Security Products 08.2006...
  • Page 6: Manufacturer's Declaration Of Conformity

    89/336/EEC “Directive of Electromagnetic Compatibility” and 73/23/EEC “Low Voltage Directive”. The EU declaration of conformity is available to the responsible agencies at: Siemens Building Technologies Fire & Security Products GmbH & Co. oHG D-76181 Karlsruhe European Directive 89/336/EEC „Electromagnetic Compatibility”...
  • Page 7: General Guidelines

    This will prevent damage to the video product due to lightning and power-line surges. Overloading: Do not overload power supply and extension cords as this can result in a risk of fire or electrical shock. Siemens Building Technologies Fire Safety & Security Products 08.2006...
  • Page 8 The exclamation point within an equilateral triangle is intended to alert the user CAUTION to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance. NOTE Tips and information. Siemens Building Technologies Fire Safety & Security Products 08.2006...
  • Page 9: Operation And Storage

    Jagged picture When viewing stripes, straight lines, or similar patterns, the image on the screen may appear jagged. Siemens Building Technologies Fire Safety & Security Products 08.2006...
  • Page 10: Technical Data

    Digital zoom 4 x (max.) Aperture correction HIGH, MID, LOW White balance AUTO: Color temperature ranges are depending on preset mode. Manual: 40 steps by push button for R and B Siemens Building Technologies Fire Safety & Security Products 08.2006...
  • Page 11 Preset: IN Door (2900 °K – 6500 °K), OUT Door (2900 °K – 9500 °K) Default settings Default setting restored by pushing the DEFAULT button Remote control RS-485: Siemens-B/ -S/ -U protocol, MOLYNX-D Twisted Pair Video Twisted Pair Video out Alarm IN Alarm OUT...
  • Page 12: Ordering Data

    CMOS camera Hexagonal wrench 4-pins IRIS plug CS-C lens mount adaptor EMI core (-LX: 2 pcs, -MX: 2 pcs) CD including remote control software and detailed Configuration Manual Quick Installation Manual Siemens Building Technologies Fire Safety & Security Products 08.2006...
  • Page 13: Camera Part And Connector Definition

    Control switch for Video Twisted Pair and RS485 External control terminal Y/C terminal OSD control button PC connection port, for factory test only Shield / GND DC12 V- or AC 24 V DC12 V+ or AC 24 V Siemens Building Technologies Fire Safety & Security Products 08.2006...
  • Page 14: Connector Pin Definition

    DC Lens 1. Damp - 2. Damp + 3. Drive + 4. Drive - 5.2.4 Y / C terminal Y (Luminance, 1 Vpp, 75 Ohm) C (Chrominance, 0,3 Vpp, burst, 75 Ohm) Siemens Building Technologies Fire Safety & Security Products 08.2006...
  • Page 15: External Control Terminal

    When Alarm IN & GND be shorted, the alarm function will be active (please set ALARM FUNC to ON in OSD menu). Alarm out Alarm out Twist pair + Twisted Pair Video output signal. Twist pair - Siemens Building Technologies Fire Safety & Security Products 08.2006...
  • Page 16: Osd Setting Hierarchy

    Camera part and connector definition OSD setting hierarchy Siemens Building Technologies Fire Safety & Security Products 08.2006...
  • Page 17 Camera part and connector definition Siemens Building Technologies Fire Safety & Security Products 08.2006...
  • Page 18: Install The Camera

    Connect suitable twisted pair receiver device (i.e. TP-RXMOD2) Setup TP transmitter using DIP-switches, please refer to chapter 5.2.1. Adjust twisted pair receiver to get best quality video-output, please refer to the instruction manual of used twisted pair receiver Siemens Building Technologies Fire Safety & Security Products 08.2006...
  • Page 19: Function Settings

    Using the UP/ DOWN button, choose the SHUTTER OFF LENS LEVEL 5 slow shutter from OFF to X16. WB MODE AUTO GAIN 24 GAMMA 0.45 APERTURE MID WD LEVEL 5 BACK Siemens Building Technologies Fire Safety & Security Products 08.2006...
  • Page 20: Lens Level

    SHUTTER OFF LENS LEVEL 5 Using UP/ DOWN button, choose gain value WB MODE AUTO from 0 dB to 30 dB. GAIN 24 GAMMA 0.45 APERTURE MID WD LEVEL 5 BACK Siemens Building Technologies Fire Safety & Security Products 08.2006...
  • Page 21: Gamma

    After selected and then press ENTER key to PRESET INROOM leave modify Mode. <CAMERA SETUP> <D/N SETUP> <OPTION> <OTHER SETUP> <REMOTE> <PRIVACY ZONE> BLC ZONE OFF SYNC MODE INT EXIT CANCEL DEFAULT Siemens Building Technologies Fire Safety & Security Products 08.2006...
  • Page 22: D/N Mode

    Press ENTER key to enter Modify status and COLOR BAR OFF then using UP/DOWN key to select Mode after DNR OFF selected and then press Enter key to leave <BACKFOCUS> modify status. SYSTEM PAL BACK Siemens Building Technologies Fire Safety & Security Products 08.2006...
  • Page 23: Mirror

    Move the cursor to the position as shown in the MIRROR OFF figure. <DZOOM> CHROMA 3 Use UP/DOWN button to choose from -7 to 8. COLOR BAR OFF DNR OFF <BACKFOCUS> SYSTEM PAL BACK Siemens Building Technologies Fire Safety & Security Products 08.2006...
  • Page 24: Color Bar

    <MOTION> Press ENTER key to enter Modify status and BACK then using UP/DOWN key to select Mode after selected and then press Enter key to leave modify status. Siemens Building Technologies Fire Safety & Security Products 08.2006...
  • Page 25: Camera Id

    ALARM TEXT 20 sec. For delay of ALARM operate timing as ---------------------------------- shown in the figure. Alarm will be reset auto- ALARM ACTION OUT ALARM DELAY 0 matically after selected time. BACK Siemens Building Technologies Fire Safety & Security Products 08.2006...
  • Page 26: Motion

    6.2.5.9 SET ZONE POSI Setting the alarm zone position. SET ZONE > < ^ v POSI 6.2.5.10 SET ZONE SIZE Changing the alarm zone size. SET ZONE > < ^ v SIZE Siemens Building Technologies Fire Safety & Security Products 08.2006...
  • Page 27: Set Zone Move

    20 sec. For delay of Motion ALARM operate MOTION LEVEL LOW timing as shown in the figure. Alarm will be re- <MOTION AREA> set automatically after selected time MOTION TEXT ------------------------------ ALARM OUT OFF MOTION DELAY 5 BACK Siemens Building Technologies Fire Safety & Security Products 08.2006...
  • Page 28: Remote

    Enter key to leave modify status. 6.2.6.1 ADDRESS Setup camera address volume 0 – 255. 6.2.6.2 PROTOCOL Protocol include Siemens-U, Siemens-B, Siemens-S and MOLYNX-D. 6.2.6.3 BAUD RATE Baud Rate: 2400, 4800, 9600, 19200. 6.2.7 PRIVACY ZONE...
  • Page 29: Blc Zone

    D. UP Half: Backlight compensation window is like . E. LOW half: Backlight compensation window is like. F: Door Low: Backlight compensation window is like. G: Door High: Backlight compensation window is like . Siemens Building Technologies Fire Safety & Security Products 08.2006...
  • Page 30: Sync Mode

    The default is 300 deg. 6.2.10 BACK Selection of next page and last page. 6.2.11 EXIT Save all setting and exit. 6.2.12 CANCEL Reset back to original settings. 6.2.13 DEFAULT Recall factory settings. Siemens Building Technologies Fire Safety & Security Products 08.2006...
  • Page 31: Maintenance

    Maintenance Maintenance Defective modules should be sent to the nearest Siemens office to be forwarded to the service centre. Disposal All electrical and electronic products should be disposed of separately from the municipal waste stream via designated collection facilities appointed by the government or the local authorities.
  • Page 32: Keyword Index

    DEFAULT 30 REMOTE 28 Dimensions 10 DNR 24 DZOOM 23 Safety precautions 5 SHUTTER 19 SYNC MODE 30 EXIT 30 SYSTEM 24 EXPOSURE 19 Transportation 9 Function setting 19 WB MODE 20 Siemens Building Technologies Fire Safety & Security Products 08.2006...
  • Page 33 Siemens Building Technologies Fire Safety & Security Products 08.2006...
  • Page 34 Issued by © 2006 Copyright by Siemens Building Technologies Siemens Building Technologies AG Fire & Security Products GmbH & Co. oHG Data and design subject to change without notice. D-76181 Karlsruhe Supply subject to availability. Printed in the Federal Republic of Germany www.sbt.siemens.com...