Toshiba MMU-AP0072H2UL Engineering Data Book page 211

208/230 v, 60 hz; 460 v, 60 hz
Hide thumbs Also See for MMU-AP0072H2UL:
Table of Contents

Advertisement

6
Indoor unit
MMD-AP0154SPH2UL, AP0184SPH2UL
Caution
The fresh air shall be conditioned by heat reclaim ventilator or similar.
Ensure the fresh air flow rate is determined so that mixed suction air and fresh air maintain the
operating temperature .
*1 Recommended conditioned air temperature is 53.6 °F to 86 °F.
However, make a fresh air flow rate within 20 % of standard.
Model name
MMD-AP0154SPH2UL
MMD-AP0184SPH2UL
Install a air filter within the fresh air duct. (Fresh air does not pass through the filter of Indoor unit.)
Insulate the fresh air duct.
Electrically connect the fan of the Heat exchanger unit and the Indoor unit to a single isolator.
0.3
0.25
0.2
0.15
0.1
0.05
0
0
10
Indoor unit
Inter - lock circuit
Connect the driving relay of the duct fan (DC 12V) between 1 and 6 on the indoor P.C. board.
(Rated current of the relay for duct fan should be up to 75 mA.)
After installation, carry out a test run to check that the duct fan of the indoor unit start/stop
simultaneously.
(Carry out the test run following the installation manual of the indoor unit.)
Standard air flow (cfm)
406
459
20
30
40
50
Fresh Air flow (cfm)
Duct fan
motor
Flange option: TCB-F101URLU
210
AP015
60
70
80
90
Fresh air
AP018
100
110