Toshiba MMU-AP0072H2UL Engineering Data Book page 88

208/230 v, 60 hz; 460 v, 60 hz
Hide thumbs Also See for MMU-AP0072H2UL:
Table of Contents

Advertisement

5
Outdoor unit
Model
Appearance
name
Size: 2.80 × 3.35 (in)
Application
* Install the optional
PCB in the inverter
assembly of the
outdoor header unit.
Enhanced Specifications
(Wiring example)
Header outdoor unit
Optional PCB
Display
Outdoor unit
relay
interface PCB
CN513
PJ17
SW07
ON
OFF
1 2 3 4
Bit 2 ON
Connection cable (attached in this optional PCB)
<SW07 (bit 2) ON [4-stage switching]>
Input
SW07 (bit 1)
SW1
SW2
Bit 1 OFF
100% (normal
OFF
OFF
operation)
Approx. 80% (upper
ON
OFF
limit regulated)
Approx. 60% (upper
OFF
ON
limit regulated)
ON
ON
0% (forced stop)
87
Function
L1: Display lamp during power peak cut control
Locally procured
TB1
L1
Shield
[OPERATION]
wire
TB2
COM
[ON]
ON
COM
[OFF]
OFF
Shield
wire
For SW1 and SW2, be sure to
provide no-voltage contacts for
each terminal.
Display relay
Bit 1 ON
100% (normal
operation)
Approx. 85% (upper
limit regulated)
Approx. 75% (upper
limit regulated)
Approx. 60% (upper
limit regulated)
Power
supply
SW 1
SW 2
(L1)
OFF
ON
ON
ON