AIR CONDITIONER (MULTI TYPE)

Installation Manual

Indoor Unit
Model name:
Floor Standing Type
MMF-AP0156H-E
MMF-AP0186H-E
MMF-AP0246H-E
MMF-AP0276H-E
For commercial use
MMF-AP0366H-E
MMF-AP0486H-E
MMF-AP0566H-E
English

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba MMF-AP0156H-E

  • Page 1: Installation Manual

    AIR CONDITIONER (MULTI TYPE) Installation Manual Indoor Unit For commercial use Model name: Floor Standing Type MMF-AP0366H-E MMF-AP0156H-E MMF-AP0186H-E MMF-AP0486H-E MMF-AP0566H-E MMF-AP0246H-E MMF-AP0276H-E English...
  • Page 2: Table Of Contents

    Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
  • Page 3: Warning Indications On The Air Conditioner Unit

    Stop the unit before the servicing. (Unit: mm) Model name X(mm) Y(mm) Z(mm) Total weight (kg) CAUTION MMF-AP0156H-E CAUTION MMF-AP0186H-E Do not touch the aluminum Do not touch the aluminium fins of the unit. MMF-AP0246H-E fins of the unit. Doing so may result in injury.
  • Page 4: Precautions For Safety

    – 3 – Precautions for safety Installation • Install the air conditioner securely in a location where the base can sustain the weight adequately. If the strength is not enough, the unit may fall down resulting in injury. The manufacturer shall not assume any liability for the damage caused by not observing the description of this •...
  • Page 5 Test run CAUTION • Before operating the air conditioner after having completed the work, check that the electrical control box cover of the indoor unit and service panel of the outdoor unit are closed, and set the circuit breaker to the ON position. You may New Refrigerant Air Conditioner Installation receive an electric shock if the power is turned on without first conducting these checks.
  • Page 6: Accessory Parts

    – 5 – Accessory parts Selection of installation place Avoid installing in the following places. Attached position Part name Q’ty Shape Stored position Select a location for the indoor unit where the cool or warm air will circulate evenly. Avoid installation in the following kinds of locations. Upper part of main unit Bracket for fixing to wall •...
  • Page 7: Installation

    Installation  Installation space (Unit: mm) Reserve sufficient space required for installation or service work.  Installation of indoor unit CAUTION 500 or more 200 or more Fixing to the wall surface Strictly comply with the following rules to prevent damage of the indoor units and human injury.
  • Page 8: Drain Piping

    – 7 – Drain piping  Installation of remote (Unit: mm) Model MMF- controller (Sold separately) AP015H to AP027H type 42 to 92 CAUTION For installation of the wired remote controller, follow the AP036H to AP056H type 52 to 102 Installation Manual attached with the remote controller.
  • Page 9  Connecting drain pipe • To connect drain hose on left The following materials for piping work and insulating process are procured locally. Refrigerant Drain pan piping Drain pan Heat insulator PVC pipe (Drain piping) Hart polyvinyl chloride pipe Drain hose Drain hose Adhesion for hart polyvinyl Fix with banding band.
  • Page 10: Refrigerant Piping

    – 9 – Refrigerant piping  Open the valve fully • Use two wrenches to connect the indoor unit pipe. Open the valve of the outdoor unit fully. Projection margin in flaring: B (Unit: mm) CAUTION Outer dia. of Conventional ...
  • Page 11: Electrical Connection

    Electrical connection ▼ Power supply 220 V – 240 V ~, 50 Hz Power supply 220 V ~, 60 Hz REQUIREMENT WARNING Power supply switch / circuit breaker or power supply wiring / fuse rating for indoor units should be selected by the accumulated total current values of the indoor units.
  • Page 12: Address Setup

    – 11 –  Wiring between indoor and outdoor units  Wire connection Indoor / Outdoor control wire / Remote controller terminal block Power supply NOTE REQUIREMENT terminal block An outdoor unit connected with control wiring between indoor and outdoor units wire becomes automatically the •...
  • Page 13: Applicable Controls

    Applicable controls  Filter sign setting Each time button is pushed, indoor unit numbers in the control group change cyclically. Select the indoor unit to change According to the installation condition, the filter sign  Basic procedure for changing REQUIREMENT settings for.
  • Page 14: Test Run

    – 13 – Test run  Remote controller sensor Wired remote controller Wireless remote controller (TCB-AX32E2) 2, 4 The temperature sensor of the indoor unit senses room When TEMPORARY button is pushed for 10 temperature usually. Set the remote controller sensor ...
  • Page 15: Maintenance

    Maintenance Take out the air filter. CAUTION • Pull up the air filter toward you. • Do not start the air conditioner while leaving air filter removed. <Daily maintenance> • Push the filter reset button. ( indication will be turn off.) ▼...
  • Page 16: Troubleshooting

    – 15 – Troubleshooting  Confirmation and check  Confirmation of error log When an error occurred in the air conditioner, an error When an error occurred on the air conditioner, the error code and indoor UNIT No. appear on the display part log can be confirmed with the following procedure.
  • Page 17 Check method On the wired remote controller, central control remote controller and the interface P.C. board of the outdoor unit (I/F), a check display LCD (Remote controller) or 7-segment display (on the outdoor interface P.C. board) to display the operation is provided.
  • Page 18 – 17 – Check code Wireless remote controller Outdoor unit 7-segment display Sensor block display of receiving unit Check code name Judging device Wired remote controller display Auxiliary code Operation Timer Ready Flash — — Indoor unit TC2 sensor error Indoor unit —...
  • Page 19 Check code Wireless remote controller Outdoor unit 7-segment display Sensor block display of receiving unit Check code name Judging device Wired remote controller display Auxiliary code Operation Timer Ready Flash — — Duplicated indoor units with priority (Displayed in indoor unit with priority) Duplicated indoor units with priority (Displayed in unit other than indoor unit with No.
  • Page 20 Batch alarm of general-purpose equipment control interface General-purpose equipment, I/F Alarms occur according to the type of error Group control follower unit error TCC-LINK — — (L20 is displayed.) Duplicated addresses of indoor units in TCC-Link central device TCC-LINK: TOSHIBA Carrier Communication Link. 37-EN 38-EN...
  • Page 21: Specifications

    Hereby declares that the machinery described below: * Under 70 dBA Generic Denomination: Air Conditioner Model / type: MMF-AP0156H-E, MMF-AP0186H-E, MMF-AP0246H-E, MMF-AP0276H-E, MMF-AP0366H-E, MMF-AP0486H-E, MMF-AP0566H-E Commercial name: Super Modular Multi System Air Conditioner Super Heat Recovery Multi System Air Conditioner Mini-Super Modular Multi System Air Conditioner (MiNi-SMMS series) Complies with the provisions of the “Machinery”...
  • Page 22 – 21 – Warnings on Refrigerant Leakage Important Check of Concentration Limit The room in which the air conditioner is to be installed requires a design that in the event of refrigerant 2) When there is an effective opening with the adjacent room for ventilation of leaking refrigerant gas (opening gas leaking out, its concentration will not exceed a set limit.