Toshiba Super Modular Unit MMU-AP0091H Installation Manual

Toshiba Super Modular Unit MMU-AP0091H Installation Manual

Hide thumbs Also See for Super Modular Unit MMU-AP0091H:

Advertisement

INSTALLATION MANUAL
Indoor Unit
4-way Air Discharge Cassette Type
MMU-AP0091H, AP0121H, AP0151H,
MMU-AP0181H, AP0241H, AP0271H,
MMU-AP0301H, AP0361H, AP0481H
MMU-AP0561H
2-way Air Discharge Cassette Type
MMU-AP0071WH, AP0091WH, AP0121WH,
MMU-AP0151WH, AP0181WH, AP0241WH,
MMU-AP0271WH, AP0301WH, AP0481WH*
1-way Air Discharge Cassette Type
MMU-AP0071YH, AP0091YH, AP0121YH,
MMU-AP0151SH, AP0181SH, AP0241SH
Slim Duct
MMD-AP0071SPH, AP0091SPH, AP0121SPH,
MMD-AP0151SPH, AP0181SPH,
MMD-AP0071SPH(SH)-C*, AP0091SPH(SH)-C*,
MMD-AP0121SPH(SH)-C*, AP0151SPH(SH)-C*,
MMD-AP0181SPH(SH)-C*,
MMD-AP0071SPH-K**, AP0091SPH-K**,
MMD-AP0121SPH-K**, AP0151SPH-K**,
MMD-AP0181SPH-K**,
Concealed Duct Standard Type
MMD-AP0071BH, AP0091BH, AP0121BH,
MMD-AP0151BH, AP0181BH, AP0241BH,
MMD-AP0271BH, AP0301BH, AP0361BH,
MMD-AP0481BH, AP0561BH
Concealed Duct High Static Pressure Type
MMD-AP0181H, AP0241H, AP0271H,
MMD-AP0361H, AP0481H, AP0721H,
MMD-AP0961H
Under Ceiling Type
MMC-AP0151H, AP0181H, AP0241H,
MMC-AP0271H, AP0361H, AP0481H
High Wall Type
MMK-AP0071H, AP0091H, AP0121H,
MMK-AP0151H, AP0181H, AP0241H,
MMK-AP0072H*, AP0092H*, AP0122H*
Floor Standing Cabinet Type
MML-AP0071H, AP0091H, AP0121H,
MML-AP0151H, AP0181H, AP0241H
Floor Standing Concealed Type
MML-AP0071BH, AP0091BH, AP0121BH,
MML-AP0151BH, AP0181BH, AP0241BH
Floor Standing Type
MMF-AP0151H, AP0181H, AP0241H,
MMF-AP0271H, AP0361H, AP0481H,
MMF-AP0561H
* CHINA market only
* CHINA market only
** KOREA market only
* European market only
FILE NO. A03-012
R410A
Outdoor Unit
Cooling Only Model
Inverter Unit
MMY-MAP0501T8, MAP0601T8
MMY-MAP0801T8, MAP1001T8
MMY-MAP1201T8
Heat Pump Model
Inverter Unit
MMY-MAP0501HT8, MAP0601HT8
MMY-MAP0801HT8, MAP1001HT8
MMY-MAP1201HT8
Heat Pump Model
Inverter Unit
MMY-MAP0501HT7, MAP0601HT7
MMY-MAP0801HT7, MAP1001HT7
MMY-MAP1201HT7
PRINTED IN JAPAN, Sep, 2004 ToMo

Advertisement

loading

Summary of Contents for Toshiba Super Modular Unit MMU-AP0091H

  • Page 1 FILE NO. A03-012 INSTALLATION MANUAL R410A Indoor Unit Outdoor Unit 4-way Air Discharge Cassette Type MMU-AP0091H, AP0121H, AP0151H, Cooling Only Model MMU-AP0181H, AP0241H, AP0271H, Inverter Unit MMU-AP0301H, AP0361H, AP0481H MMY-MAP0501T8, MAP0601T8 MMU-AP0561H MMY-MAP0801T8, MAP1001T8 2-way Air Discharge Cassette Type MMY-MAP1201T8 MMU-AP0071WH, AP0091WH, AP0121WH, MMU-AP0151WH, AP0181WH, AP0241WH, MMU-AP0271WH, AP0301WH, AP0481WH*...
  • Page 2: Warnings On Refrigerant Leakage

    WARNINGS ON REFRIGERANT LEAKAGE Refrigerant density limit The room in which the air conditioner is to be installed should be designed or chosen such that in the event of a refrigerant gas leak the density of gas should not exceed a set limit. The refrigerant R-410A, which is used in the air conditioner product, is intrinsically safe without the toxicity or combustibility of ammonia.
  • Page 3 Note 3: The minimum indoor floor area compared with the amount of refrigerant is roughly as follows (when the Range below the ceiling is 2.7 m high): density limit of 0.3 kg/m (countermeasures not needed) Range above the density limit of 0.3 kg/m (countermeasures needed...
  • Page 4: Table Of Contents

    CONTENTS WARNINGS ON REFRIGERANT LEAKAGE ..........2 SAFETY CAUTION ................... 5 1. SELECTING A LOCATION FOR INSTALLATION ........9 2. SAFETY NOTES..................16 3. CHECK POINTS ..................17 4. KEY POINTS OF AIR CONDITIONER INSTALLATION ......18 5. REFRIGERANT PIPE INSTALLATION ..........19 6.
  • Page 5: Safety Caution

    SAFETY CAUTION Important safety information is displayed on the product and in this Installation Manual. Please ensure this is read thoroughly and keep for future reference. Before any repairs or maintenance is carried out an assessment of the potential risks must be undertaken, and appropriate measures taken to ensure the safety of all personnel.
  • Page 6 WARNING Check earth wires Before troubleshooting or repair work, check the earth wire is connected to the earth terminals of the unit, otherwise electric shock could occur. • If the earth is not correctly connected, turn off the system and contact an electrical engineer.
  • Page 7 WARNING Insulation check Ensure that the electrical insulation is intact before energising. • After the installation is complete, carry out an insulation resistance test (using a 500 V DC Megger), to check the resistance is 2 MΩ or more between each electrically charged section (phase) and the metal chassis (Earth).
  • Page 8 New refrigerant (R-410A) This air conditioner features a new HFC type refrigerant (R-410A) which does not deplete the ozone layer. 1. Safety caution concerned with new refrigerant The pressure of R-410A is 1.6 times higher than that of former refrigerant R-22. The refrigerating oil has also been changed.
  • Page 9: Selecting A Location For Installation

    1. SELECTING A LOCATION FOR INSTALLATION WARNING The installation of the air conditioning unit must be positioned in a location that can sufficiently support its weight and give protection against adverse environmental conditions. Failure to do so may result in unit damage and possible human injury. All cassette type and concealed duct air conditioner units must be installed at a minimum height of 2.5m or more from the floor.
  • Page 10 Combination of outdoor unit Cooling Only Model No. of Model name Inverter 5HP Used Inverter 6HP Used Inverter 8HP Used Inverter 10HP Used Inverter 12HP Used (Capacity combined MMY- MMY- MMY- MMY- MMY- MMY- code) units 5HP ( 5) MAP0501T8 MAP0501T8 6HP ( 6) MAP0601T8...
  • Page 11 Heat-pump Model (60Hz) No. of Model name Inverter 5HP Used Inverter 6HP Used Inverter 8HP Used Inverter 10HP Used Inverter 12HP Used (Capacity combined MMY- MMY- MMY- MMY- MMY- MMY- code) units 5HP ( 5) MAP0501HT7 MAP0501HT7 6HP ( 6) MAP0601HT7 MAP0601HT7 8HP ( 8)
  • Page 12 2. Outdoor units (Combination of outdoor units) Corresponding HP 5 HP 6 HP 8 HP 10 HP 12 HP 14 HP 16 HP MMY- MAP0501HT8 MAP0601HT8 MAP0801HT8 MAP1001HT8 MAP1201HT8 AP1401HT8 AP1601HT8 Combined Model MMY- MAP0501HT7 MAP0601HT7 MAP0801HT7 MAP1001HT7 MAP1201HT7 AP1401HT7 AP1601HT7 MMY- MAP0501T8...
  • Page 13 3. Indoor units *1) China market only *2) European market only *3) Korea market only Capacity Cooling Heating Type Appearance Model name Capacity rank code capacity (kW) capacity (kW) MMU-AP0091H 009 type MMU-AP0121H 012 type 1.25 MMU-AP0151H 015 type MMU-AP0181H 018 type MMU-AP0241H 024 type...
  • Page 14 *1) China market only *2) European market only *3) Korea market only Capacity Cooling Heating Type Appearance Model name Capacity rank code capacity (kW) capacity (kW) MMC-AP0151H 015 type MMC-AP0181H 018 type MMC-AP0241H 024 type Under Ceiling Type MMC-AP0271H 027 type MMC-AP0361H 036 type 11.2...
  • Page 15 4. Tools • Required tools for R-410A Mixing of different types of oil may cause generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types: 1) Tools exclusively for R-410A, which cannot be used for conventional refrigerant R-22. 2) Tools exclusively for R-410A, but can also be used for conventional refrigerant R-22.
  • Page 16: Safety Notes

    2. SAFETY NOTES • Ensure that all Local, National and International regulations are satisfied. • After the installation work has been completed, perform a trial operation to check for possible problems. Follow the owner's manual to explain how to use and maintain the unit to the customer. •...
  • Page 17: Check Points

    3. CHECK POINTS Check before operation • Turn on the main power supply 12 hours or more before starting the operation. • Check and ensure earth wiring is connected. • Check and ensure air filter is fitted to indoor unit. Heating capacity •...
  • Page 18: Key Points Of Air Conditioner Installation

    4. KEY POINTS FOR AIR CONDITIONER INSTALLATION In order to prevent problems before they arise, carefully read the Installation Manual provided with the equipment and the Owner’s Manual before installing the air conditioner. 4-1. Flow of Air Conditioner Installation Work [Step] [Key Points] (Prior to Installation)
  • Page 19: Refrigerant Pipe Installation

    5. REFRIGERANT PIPE INSTALLATION 5-1. Work Procedure Flaring Indoor unit Sizing Preliminary installation the pipes installation Nitrogen gas blow Vacuum Leak test Flushing suction Brazing 5-2. Three Principles of Refrigerant Pipes Observe the three principles of refrigerant pipes Causes of Problems Preventing Problems •...
  • Page 20 5-3. Selecting the Refrigerant pipework Material • Refrigerant pipes • Material: Phosphoric deoxidized seam-less pipe • Capacity code of outdoor unit / indoor unit • For each indoor unit, the capacity code is determined for each capacity rank. • For each outdoor unit, the capacity code is determined for each capacity rank. The maximum number of the connectable indoor units and the total capacity code value of the indoor units must also be determined.