4. Mini VRF System Alarm Codes
3. Mini VRF System Alarm Codes
H01 Primary Current (Input) Detect of Overcurrent
1.
Error Detection Method
Primary current effective value detected overcurrent (trip current value).
Trip current value
Single-phase model
Heating
Cooling
2.
Error Diagnosis
1 Power
1-1
Not satisfied with ±10% rated supply voltage
supply*
1-2
Extreme voltage fluctuations
1-3
Extreme distortion of voltage waveform
1-4
Instantaneous blackout may sometimes occur.
2
PC board
Has FUSE 1 blown?
2-1
wiring
Check the electrical conduction with tester.
2-2
Loose electrical wire connection
2-3
Replace CR board.
*
Check not only in the outdoor unit stop mode but in the drive mode.
(for single-phase outdoor unit PC board)
hp = horsepower
4 hp
5 hp
6 hp
23.0A
26.5A
30.0A
22.0A
25.0A
28.0A
FUSE 1
Trip current value
3-phase model
4 hp
Heating
10.5A
Cooling
10.5A
(for 3-phase outdoor unit PC board)
5 - 31
Mini VRF SYSTEM
Mini VRF SYSTEM
Trouble Diagnosis
Trouble Diagnosis
hp = horsepower
5 hp
6 hp
12.0A
14.0A
12.0A
14.0A
Yes
Check power supply
No
1-2
Yes
Check power supply
No
1-3
Yes
Check power supply
No
1-4
Yes
Check power supply
No
2-1
2-3
Yes
No
2-2
Yes
Correct wiring
No
2-3
FUSE 1
5