Mains Power Connections; Relay Output Board Connections; Hybrid I/O Module Connections; Digital Output Connections - ABB SM1000 User Manual

Videographic recorder
Hide thumbs Also See for SM1000:
Table of Contents

Advertisement

...5 INSTALLATION
5.6 Mains Power Connections – Fig 5.9
Fuse,
1A, Type T
Line
Neutral
Terminal Block E
Caution. Use fuse rating – 1A (max.) type T.
A - A.C. Supply
Fuse,
3A, Type T
+
24V dc
-
Terminal Block E
Caution. Use fuse rating – 3A (max.) type T.
B - D.C. Supply
Fig. 5.9 Mains Power Supply
5.7 Relay Output Board Connections – Fig. 5.10
Note.
• The maximum total combined current flowing through the
relays is 36A. The maximum individual relay current is 5A.
• The polarity is setup during I/O module configuration –
see Section 4.7.2, 3-Relay and 6-Relay Modules.
17
14
11
18
15
12
19
16
13
Terminal Block C or D
Note. Relay contacts are fitted with arc
suppression components as standard.
Fig. 5.10 Relay Connections
74
L
85 – 265V
N
50/60Hz
1
2
3
4
5
7
4
1
8
5
2
9
6
3

5.8 Hybrid I/O Module Connections

5.8.1 Digital Output Connections – Fig 5.11
Six digital outputs are provided on the Hybrid option board.
do1
9
do2
10
do3
11
do4
12
do5
13
do6
14
COM
15
COM
16
Information.
Voltage level 5V. Load: 450Ω min. 15kΩ max.
Note. Refer to Fig. 5.5 for terminal numbers.
Fig. 5.11 Digital Output Connections
5.8.2 Digital Input Connections – Fig 5.12
Six digital inputs are provided on Hybrid option boards.
Terminal Blocks C or D
di1
1
2
di2
3
di3
4
di4
5
di5
6
di6
7
COM
8
COM
Input State
Switch Input
Logic Input
or
0V
or
5V
Fig. 5.12 Digital Input Connections
5.8.3 Analog Output Connections – Fig 5.13
Two analog outputs are provided on the Hybrid option board.
17
18
19
20
Fig. 5.13 Analog Output Connections
Digital Output
Load
Common
or
5V
0V
Logic State
Dxx active
Dxx in-active
+
a01
+