Appendix 2 Instructions for UL and cUL

(Conforming standard UL 508C, CSA C22.2 No.14)
(1) Installation
This inverter is UL-listed as a product for use in an enclosure.
Design an enclosure so that the inverter ambient temperature, humidity and atmosphere satisfy the specifications.
(Refer to page 161.)
Wiring protection
For installation in the United States, branch circuit protection must be provided in accordance with the National
Electrical Code and any applicable provincial codes.
For installation in Canada, branch circuit protection must be provided in accordance with the Canada Electrical Code
and any applicable provincial codes.
Use the Class RK5, Class T or L type fuses certified by UL and cUL.
FR-A720-
K
Rated voltage(V)
Without power
factor improving
Rated
reactor
current
With power
(A)
factor improving
reactor
FR-A720-
K
Rated voltage(V)
Without power
factor improving
Rated
reactor
current
With power
(A)
factor improving
reactor
FR-A740-
K
Rated voltage(V)
Without power
factor improving
Rated
reactor
current
With power
(A)
factor improving
reactor
FR-A740-
K
Rated voltage(V)
Without power
factor improving
Rated
reactor
current
With power
(A)
factor improving
reactor
(2) Wiring of the power supply and motor
For wiring the input (R/L1, S/L2, T/L3) and output (U, V, W) terminals of the inverter, use the UL-listed copper wires
(rated at 75°C) and round crimping terminals. Crimp the crimping terminals with the crimping tool recommended by the
terminal maker.
(3) Short circuit ratings
• 200V class
Suitable For Use in A Circuit Capable Of Delivering Not More Than 100kA rms Symmetrical Amperes, 264V Maximum.
• 400V class
55K or less
Suitable For Use in A Circuit Capable Of Delivering Not More Than 100kA rms Symmetrical Amperes, 528V Maximum.
75K or more
Suitable For Use in A Circuit Capable Of Delivering Not More Than 100kA rms Symmetrical Amperes, 550V Maximum.
180
0.4
0.75
1.5
2.2
15
20
30
40
15
20
20
30
75
90
240V or more
600
700
0.4
0.75
1.5
2.2
6
10
15
20
6
10
10
15
75
90
110
132
300
350
400
500
3.7
5.5
7.5
11
240V or more
60
80
150
175
50
70
125
150
3.7
5.5
7.5
11
480V or more
30
40
70
80
25
35
60
70
160
185
220
250
500V or more
600
700
800
900
15
18.5
22
30
200
225
300
350
200
200
250
300
15
18.5
22
30
90
110
150
175
90
100
125
150
280
315
355
400
1000
1100
1200
1350
37
45
55
400
500
500
350
400
500
37
45
55
200
250
300
175
200
250
450
500
1500
1800