13. External input/output function

• External signal input requires the external I/O adapter (PAC-YG10HA-E; sold separately).
• If an Expansion controller is connected, the external input/output function can be set to use only the Expansion controller.
• Refer to the Installation Manual and the Instructions Book for the unit and Expansion controller (PAC-YG50ECA) for details.
• ON/OFF batch operation of external input function cannot be used on DIDO controller (PAC-YG66DCA). However, only when
"Emergency Stop (Level signal)" is selected, batch operation can be used by setting switches on DIDO controller (PAC-YG66DCA).
• External input function cannot be used on HWHP (CAHV).

13-1 External input function

(1) The function of external input
Touch [Initial Settings] on the menu bar in the setting change screen, then [Network setting] to bring up the network settings screen.
Touch [External Input Setting], and make the settings.
• The type of external input function can be selected by making certain settings.
Function of external input signal
External input signal not used
Perform emergency stop with level
signal
Perform ON/OFF operation with level
signal
Perform ON/OFF operation, prohibit/
permit operation with pulse signal
(2) Input signal
1 Level signal
2 Pulse signal
(Example) ON/OFF
• Signal 1 (ON)
• Signal 2 (OFF)
(3) Specification of external input interface
CN5
Lead wire
No.5
Orange
No.6
Yellow
No.7
Blue
No.8
Gray
No.9
Red
Button
Do not use
Emergency Stop
(Level signal)
ON/OFF
(Level signal)
ON/OFF/Prohibit/Permit
(Pulse signal)
Contact ON
Contact OFF
Normal
Contact ON
Contact OFF
Contact ON
Contact OFF
OFF
Emergency stop/normal level signal
Emergency stop/normal input
Not used
Not used
Not used
During emergency stop, only ON/OFF of the centralized controller
and local remote controller operation will be prohibited. Scheduled
operations cannot be performed.
Only the ON/OFF operation of the centralized controller and the
local remote controller will be prohibited. Scheduled operations
cannot be performed.
Set the pulse width when the contact is ON between 0.5 and 1.0
seconds.
Emergency stop
Emergency stop
Normal
ON
ON/OFF level signal
ON/OFF input
Not used
Not used
Not used
External DC source "+12VDC" or "+24VDC"
– 105 –
Remarks
-
ON/OFF with level
Signal input
OFF
ON
* Set the pulse width to a value between 0.5 and
1.0 second.
* Applicable also to the input signal that
prohibits/permits operation.
OFF
ON/OFF, prohibit/permit pulse signal
Local remote controller prohibit input
Local remote controller permit input
OFF
ON input
OFF input