3.4.3

Time Delayed Measured Earth Fault Protection (51G)

Two time delayed measured earth fault elements are provided in the 7SR21 relay. Four elements are provided in
the 7SR22 relay e.g. giving the option of using two elements set to forward and two to reverse.
51G-n Setting sets the pick-up current level.
A number of shaped characteristics are provided. An inverse definite minimum time (IDMT) characteristic is
selected from IEC and ANSI curves using 51G-n Char. A time multiplier is applied to the characteristic curves
using the 51G-n Time Mult setting. Alternatively, a definite time lag (DTL) can be chosen using 51G-n Char.
When DTL is selected the time multiplier is not applied and the 51G-n Delay (DTL) setting is used instead.
The 51G-n Reset setting can apply a definite time delayed reset, or when configured as an ANSI characteristic
an ANSI (DECAYING) reset. If ANSI (DECAYING) reset is selected for an IEC characteristic, the reset will be
instantaneous. The reset mode is significant where the characteristic has reset before issuing a trip output – see
'Applications Guide'.
A minimum operate time for the characteristic can be set using 51G-n Min. Operate Time setting.
A fixed additional operate time can be added to the characteristic using 51G-n Follower DTL setting.
Where directional elements are present the direction of operation can be set using 51G-n Dir. Control setting.
Directional logic is provided independently for each 51G-n element.
Operation of the time delayed measured earth fault elements can be inhibited from:
Inhibit 51G-n
79 E/F Inst Trips: 51G-n
51G-n Inrush Action: Inhibit
51G-n VTSAction: Inhibit

Figure 3.4-3 Logic Diagram: Measured Time Delayed Earth Fault Element (51G)

©2010 Siemens Protection Devices Limited
7SR21 & 7SR22 Argus Description of Operation
A binary or virtual input, or function key
When 'delayed' trips only are allowed in the auto-reclose sequence
(79 E/F Prot'n Trip n = Delayed).
Operation of the inrush current detector function.
Operation of the VT Supervision function (7SR22).