3–4 Undervoltage Release Device
The undervoltage release device (UVR), shown in Figure
28, opens the circuit breaker when the supply voltage
drops to 35–60% of its rated value. Figure 29 shows the
dropping resistor supplied with 240–600 volt UVRs. The
UVR electrical characteristics are listed in Table 6. The
UVR wiring diagram is in Figure 30.
Figure 28. Undervoltage release device.
Figure 29. Dropping resistor supplied with 240–600 V UVRs.
Figure 30. UVR wiring diagram.
Catalog
Voltage
Number
Rating
TPUV1S
120 Vac
TPUV2S
240 Vac
TPUV2S
480 Vac
TPUV6S
600 Vac
TPUV7S
12 Vdc
TPUV8S
24 Vdc
TPUV9S
48 Vdc
TPUV10S
125 Vdc
TPUV11S
250 Vdc
* Ohmite Type 270
Table 6. UVR electrical characteristics.

UVR Installation

1 1 1 1 . . . . Remove the circuit breaker cover(s) as described
above in 3–2 Circuit Breaker Cover .
2 2 2 2 . . . . The UVR assembles to a mounting plate. Not all
breakers are shipped from the factory with a mount-
ing plate. Some breakers have only an L-shaped
bracket to retain the molded-plastic crank. A mount-
ing plate is provided in the UVR kit.
• If the breaker is supplied with an L-shaped
bracket, remove the two retaining screws and dis-
card the bracket. Follow the Mounting Plate
Installation instructions and continue on to step
3.
• If the breaker is supplied with a mounting plate,
continue with step 3.
3 3 3 3 . . . . Remove the slide reset lever spring from the mount-
ing plate, as shown in Figure 31. Be careful not to
nick or damage the spring in any way, since it will be
needed for reassembly.
4 4 4 4 . . . . Push the latch and slide reset lever forward to pro-
vide mounting clearance for the UVR assembly.
5 5 5 5 . . . . Position the UVR assembly mounting bracket so that
its retaining hole engages the latch pivot post, as
shown in Figure 32.
6 6 6 6 . . . . Line up the UVR bracket's mounting hole with the
tapped hole in the accessory mounting plate. Install
the screw and lock washer, as shown in Figure 33.
Tighten the screw to 9–11 in-lbs.
7 7 7 7 . . . . Replace the slide reset lever spring, shown in Figure
31.
8 8 8 8 . . . . Remove the knockouts in the side of the base, as
required. Each knockout will accommodate up to
three bundles of wire. Remove all sharp edges with a
file.
9 9 9 9 . . . . Remove all debris from the inside of the breaker.
14
Continuous
Dropping
Current, mA
Resistor*
25
none
25
5000 ?, 25 W
25
15,000 ?, 50 W
25
20,000 ?, 50 W
211
none
104
none
54
none
24
none
24
5000 ?, 25 W