Environmental Conditions; Type Tests Ra33X - GE RPV311 Technical Manual

Distributed multifunction fault recorder
Table of Contents

Advertisement

RPV311
2.10

Environmental Conditions

2.11

Type Tests RA33x

RPV311-TM-EN-7
Operating temperature range
Maximum operating altitude
Relative humidity
Tested as per 60068-2-1
Tested as per 60068-2-2
EMC tests were performed according to IEC 60255-26 referring to the following
standards
IEC 61000-4-2:2008
IEC 61000-4-3:2006
IEC 61000-4-4:2012
IEC 61000-4-5:2005
IEC 61000-4-6:2008
IEC 61000-4-8:2009
IEC 61000-4-11:2004
IEC 61000-4-29:2000
Chapter 17 – Technical Specifications
RA33x Environmental Conditions
-40 ... +55 °C
2000 m (6560 ft)
5 ... 95 % noncondensing
-40°C
+85°C
Type Tests RA33x
8kV contact / 15KV air (level 4)
10 V/m (level 3)
2 KV @ 5KHz (level 3)
Differential mode: 1KV
Common mode: 2KV
(level 3)
10V
30ª/m continuos – 300ª/m @ 1s.
A.C. and d.c. voltage dips
Test level: 0% residual voltage
Duration time
a.c.: 1 cycle
d.c.: 16,6ms
270