GE RPV311 Technical Manual page 95

Distributed multifunction fault recorder
Table of Contents

Advertisement

RPV311
Data name
register number
0
1
2
3
4
VA CV1
100
VB CV1
101
VC CV1
102
VN CV1
103
VC1 CV1 mag
106
VN1 CV1 mag
107
VA1 CV1 phi
110
VS+ CV1 mag
112
VS- CV1 mag
113
RPV311-TM-EN-7
MODBUS
DNP3 Database
associated
number
00
01
02
03
04
05
06
07
08
09
10
11
12
13
Note: Whenever MODBUS/DNP3 feature is enabled, the RPV will send both types
of messages. It is not possible to enable just one protocol.
Alarms:
bit 0: Equipment NOK
bit 1: Primary power failure
bit 2: Not used
bit 3: Not used
bit 4: Equipment not synchronized
bit 5: Fault recorder low memory
bit 6: Disturbance recorder low memory
bit 7: Steady-state recorder low memory
bit 8: SOE recorder lack of memory
bit 9: Internal failure
Not used
Not used
Not used
Time quality
CV1 voltage circuit, phase A RMS value
CV1 voltage circuit, phase B RMS value
CV1 voltage circuit, phase C RMS value
CV1 voltage circuit, neutral RMS value
CV1 voltage circuit, phase C phasor magnitude
CV1 voltage circuit, neutral phasor magnitude
CV1 voltage circuit, phase A phasor angle
CV1 voltage circuit, positive sequence magnitude
CV1 voltage circuit, negative sequence magnitude
Note:
The 104, 105, 108, 109 and 111 registers (without configuration,
as shown in figure 114) have no influence DNP3 Database
analogue object number's increment
Chapter 4 – Configuration