Errors/accuracies
Linearity error (in relation to input range), (+/-)
Temperature error (in relation to input range), (+/-) 0.005%/K
Crosstalk between the inputs, max.
Repeat accuracy in settled state at 25 °C (in rela-
tion to input range), (+/-)
Temperature errors of internal compensation
Operational limit in overall temperature range
Voltage in relation to input range, (+/-)
Resistance in relation to input range, (+/-)
Resistance thermometer in relation to input range,
(+/-)
Thermocouple, relative to input range, (+/-)
Basic error limit (operational limit at 25 °C)
Voltage in relation to input range, (+/-)
Resistance in relation to input range, (+/-)
Resistance thermometer in relation to input range,
(+/-)
Thermocouple, relative to input range, (+/-)
Interference voltage suppression for f = n x (f1 +/-
1 %), f1 = interference frequency
Series-mode interference (peak of the interference
< rated value of the input range), min.
Common mode voltage, max.
Common mode interference, min.
Isochronous mode
Isochronous mode (application synchronized up to
terminal)
Interrupts/diagnostics/status information
Diagnostics function
Interrupts
Diagnostic interrupt
Limit interrupt
Diagnostics alarms
Monitoring of supply voltage
Wire break
Overflow/underflow
Analog Input Module AI 8xU/R/RTD/TC HF (6ES7531-7PF00-0AB0)
Manual, 09/2016, A5E36647959-AB
Technical specifications
6ES7531-7PF00-0AB0
0.02%
-80 dB
0.02%
+/-1.5 °C
0.1%
0.1%
Cuxxx Standard: ±0.5 K, Cuxxx Climatic: ±0.5 K,
Ptxxx Standard: ±1 K, Ptxxx Climatic: ±0.5 K,
Nixxx Standard: ±0.5 K, Nixxx Climatic: ±0.3 K
Type B: > 600 °C ±2 K, Type E: > -200 °C ±1 K,
Type J: > -210 °C ±1 K, Type K: > -200 °C ±2 K,
Type N: > -200 °C ±2 K, Type R: > 0 °C ±2 K,
Type S: > 0 °C ±2 K, Type T: > -200 °C ±1 K,
Type C: ±4 K, Type TXK/TXK(L): ±1 K
0.05%
0.05%
Cuxxx Standard: ±0.3 K, Cuxxx Climatic: ±0.2 K,
Ptxxx Standard: ±0.5 K, Ptxxx Climatic: ±0.2 K,
Nixxx Standard: ±0.3 K, Nixxx Climatic: ±0.15 K
Type B: > 600 °C ±1 K, Type E: > -200 °C ±0.5 K,
Type J: > -210 °C ±0.5 K, Type K: > -200 °C ±1
K, Type N: > -200 °C ±1 K, Type R: > 0 °C ±1 K,
Type S: > 0 °C ±1 K, Type T: > -200 °C ±0.5 K,
Type C: ±2 K, Type TXK/TXK(L): ±0.5 K
80 dB; in Standard mode, 40 dB in Fast mode
60 V DC / 30 V AC
80 dB
No
Yes
Yes
Yes; two high limits and two low limits each
Yes
Yes; only for TC. R. RTD
Yes
51