Parameter data records
B.3 Structure of data record 235 for scalable measuring range
Description of the parameters from data record 235
Table B- 16
Parameter
Scalable measuring range enabled
Clipping
Resolution
Measuring range center
Overflow/underflow
Example
The following example shows the values for a thermal resistor Pt 100 Standard, °C:
Table B- 17
Hex. value
10
H
08
H
03
H
02
H
02EE
61A8
8100
70
Description of the parameters from data record 235
Example of a thermal resistor Pt 100 Standard
Dec. value
16
8
3
2
750
H
25000
H
-32512
H
Description
1 = Function is active for this channel.
1 = Scalable measuring range cut off at the over-
flow/underflow of the underlying measuring range.
2 or 3 decimal places
Temperature in whole °C / °F / K
("working point" for the scaling)
Limits of the scalable measuring range
Evaluation of data record 235
V1.0
8 bytes
Scalable measuring range active and clipped (clipping)
Resolution: 2 decimal places
Measuring range center: 750 °C
Overflow (Maximum):
250.00 + 750 = 1000.00 °C
Scalable measuring range is clipped at the overflow.
Underflow (Minimum):
-325.12 + 750 = 424.88 °C
Analog Input Module AI 8xU/R/RTD/TC HF (6ES7531-7PF00-0AB0)
Manual, 09/2016, A5E36647959-AB