3.2.4
DS7432 Eight-Input Remote Module
DS7432s occupy groups of eight points; however,
when programming the DS7432 with the Multiplex
Point Programmer, they must be programmed as four
sets of dual points. For example, if using a DS7432 on
the system for Points 9 through 16, program Points 9,
11, 13, and 15 as dual points.
3.2.5
DS7465 Input/Output Module
The relay output number assigned to this module is
directly associated with the point number assigned to
it. For example, if this device was programmed as
Point 27, the relay number is also 27.
3.2.6
Removing a Point from the D8125MUX
1. Apply power to the D5060 and connect the
programmer to the D8125MUX only.
2. Enter the address of the point you want to
remove.
3. When prompted for a point type, press [0]. Refer
Table 20
.
to
Figure 21: D8125MUX Multiplex Bus Interface
Module
Operation LED
RESET
12V
IN
OUT
GND
FIRE MANUAL
PROG
PORT
ZONEX BUS
WALK TEST
Figure 22: Connecting the Transient Noise
Suppression Diode (P/N: NS001-20)
Cathode
end
Bosch Security Systems, Inc. | 11/05 | F01U011024B
D9412GV2/D7412GV2 | Troubleshooting Guide | 3.0 Troubleshooting
+
-
+
-
+
-
+
-
POWER B
POWER A
MUX BUS A
MUX BUS B
+ Mux Bus
- Mux Bus
Table 19: Multiplex Devices
Product
DS7432 Eight-Input Remote Module
DS7450 Flush-Mount Single Multiplex
Contact Point
DS7452 Surface-Mount Single Multiplex
Contact Point
DS7457 Single Multiplex Input Module
DS7460 Dual Zone Input Module
DS7465 Input/Output Module
MX775 (DS7470) Multiplex Passive
Infrared (PIR) Intrusion Detector – 50 ft.
(15 m) Mirror
MX934 (DS7471) Multiplex PIR Intrusion
Detector – 35 ft. (11 m) Mirror
MX938 (DS7472) Ceiling Mount Multiplex
PIR Intrusion Detector
MX540 (DS7473) Multiplex PIR Intrusion
Detector – 40 ft. (12 m) Fresnel Lens
MX794 (DS7474) Multiplex Long Range
PIR Intrusion Detector
MX950 (DS7476) Multiplex PIR/Microwave
TriTech Intrusion Detector
MX835 (DS7477) Multiplex PIR/Microwave
TriTech Intrusion Detector with Pet
Immunity
Table 20: Point Type Entry Code
Decimal Value
Point Type
0
Remove point from D8125MUX
1
Contact
2
Sensor (or Single Point Module)
3
I/O Module
4
MUX smoke without low temperature
5
MUX smoke with low temperature
6
Dual point
Point Type
6
1
1
2
6
3
2
2
2
2
2
2
2
39