Creating substation structure and communication
structure
Creating substation and communication structures with SCL
descriptions or connectivity packages
To create the substation and communication structures with SCL descriptions or con-
nectivity packages:
1. Create Substation and Voltage level objects to the substation structure.
2. Create the OPC Server and communication channel objects to the communication
structure.
3. Create the IED object below the communication channel and use either the connectiv-
ity package or IED SCL description file to populate automatically the structure
below the IED. The substation structure is automatically populated with primary
apparatus objects described in the connectivity package or SCL descriptions. You
may be prompted to give some information to guide the process, for example choose
a voltage level or give a bay name.
4. Repeat step 3 for each IED.
5. Fine-tune the SLD layout (assign colors, specify incoming/outgoing feeders, and
so on) by modifying or adding objects. Additionally you might need to create busbar
connections, see 3.4.2,  Creating substation structure manually .
6. Download the configuration to the COM600 computer.

Creating substation structure manually

The following is an overview of creating a substation structure manually. For a more
detailed description, see 3.4.3, Adding Gateway object, 3.4.4, Adding Substation,
3.4.5, Adding voltage level object, 3.4.6, Adding bay object and 3.4.7, Adding busbar
object.
Before you can create a substation structure, you have to create
a communication structure with OPC Server and communica-
tion channel objects, IEDs, Logical Devices, Logical Nodes
and Data objects.
To create the substation structure manually:
1. Create Gateway, Substation and Voltage level objects to the substation structure.
2. Add bays and busbars, and design their layout using the SLD Editor. Connect your
substation structure objects to communication structure (logical nodes) using the
data connection function, see 3.6.1, General about Data connection .