ABB Relion 670 series Product Manual

Line distance protection ansi pre-configured
Hide thumbs Also See for Relion 670 series:

Advertisement

®
Relion
670 series
Line distance protection REL670 ANSI
Pre-configured
Product Guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB Relion 670 series

  • Page 1 ® Relion 670 series Line distance protection REL670 ANSI Pre-configured Product Guide...
  • Page 2: Table Of Contents

    10. Monitoring..............18 Disclaimer © Copyright 2012 ABB. All rights reserved. Trademarks ABB and Relion are registered trademarks of ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.
  • Page 3: Application

    Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Issued: May 2012 Revision: A 1. Application The advanced logic capability, where the user logic REL670 is used for the protection, control and is prepared with a graphical tool, allows special monitoring of overhead lines and cables in solidly applications such as automatic opening of grounded networks.
  • Page 4 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 en06000378_ansi.vsd ANSI06000378 V1 EN Figure 1. The single breaker packages for single- and three-pole tripping typical arrangement for one protection sub- system is shown here.
  • Page 5 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 en06000377_ansi.vsd ANSI06000377 V1 EN Figure 2. The multi breaker packages for single- and three pole tripping typical arrangement for one protection sub- system is shown here. Auto-reclose, Synchrocheck and Breaker failure functions are included for each of the two breakers.
  • Page 6: Available Functions

    Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 2. Available functions Main protection functions = number of basic instances 3-A03 = optional function included in packages A03 (refer to ordering details) IEC 61850 ANSI Function description Distance REL670 (B32A) Differential protection...
  • Page 7: Current Protection

    Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Back-up protection functions IEC 61850 ANSI Function description Distance REL670 (B32A) Current protection PHPIOC Instantaneous phase overcurrent protection OC4PTOC 51_67 Four step phase overcurrent protection EFPIOC Instantaneous residual overcurrent protection EF4PTOC 51N_67 Four step residual overcurrent protection...
  • Page 8: Secondary System Supervision

    Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Control and monitoring functions IEC 61850 ANSI Function description Distance REL670 (B32A) Control SESRSYN Synchrocheck, energizing check and synchronizing SMBRREC Autorecloser APC15 Apparatus control for single bay, max 15 apparatuses (2CBs) incl. interlocking QCBAY Apparatus control...
  • Page 9: Metering

    Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 IEC 61850 ANSI Function description Distance REL670 (B32A) CVMMXN Measurements CNTGGIO Event counter Event Event function DRPRDRE Disturbance report SPGGIO IEC61850 generic communication I/O functions SP16GGIO IEC61850 generic communication I/O functions 16 inputs MVGGIO IEC61850 generic communication I/O functions BSStart...
  • Page 10: Local

    Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Designed to communicate IEC 61850 ANSI Function description Distance REL670 (B32A) Station communication SPA communication protocol LON communication protocol IEC60870-5-103 communication 20/1 protocol Operation selection between SPA and IEC60870-5-103 for SLM DNP3.0 for TCP/IP and EIA-485 communication protocol...
  • Page 11: Basic Ied Functions

    Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Basic IED functions IEC 61850 Function description Basic functions included in all products IntErrorSig Self supervision with internal event list TIME Time and synchronization error TimeSynch Time synchronization ActiveGroup Parameter setting groups Test...
  • Page 12 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 3. Impedance protection directional function (phase unselective, because it is based on symmetrical components). Full-scheme distance measuring, Mho characteristic ZMHPDIS (21) Mho impedance supervision logic ZSMGAPC The numerical mho line distance protection is a The Mho impedance supervision logic (ZSMGAPC) zone full scheme protection for back-up detection includes features for fault inception detection and...
  • Page 13 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Power swing detection function (ZMRPSB, 68) is of the line at minimum source impedance. EFPIOC used to detect power swings and initiate block of (50N) can be configured to measure the residual selected distance protection zones.
  • Page 14 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 All IEC and ANSI time delayed characteristics are be current based, contact based, or an adaptive available together with an optional user defined combination of these two conditions. characteristic.
  • Page 15 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 breakers should be tripped to clear the Two step residual overvoltage protection unsymmetrical load situation. ROV2PTOV (59N) Residual voltages may occur in the power system The Polediscrepancy protection function CCRPLD during ground faults.
  • Page 16 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 A detection of a difference indicates a fault in the 7. Control circuit and is used as alarm or to block protection Synchrocheck, energizing check, and functions expected to give unwanted tripping. synchronizing SESRSYN (25) The Synchronizing function allows closing of Fuse failure supervision SDDRFUF...
  • Page 17 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 8. Scheme communication Apparatus control APC The apparatus control functions are used for control Scheme communication logic for distance or and supervision of circuit breakers, disconnectors overcurrent protection ZCPSCH (85) and grounding switches within a bay.
  • Page 18 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 9. Logic The function requires that the IED is equipped with the mA input module. Tripping logic SMPPTRC (94) A function block for protection tripping is provided Event counter CNTGGIO for each circuit breaker involved in the tripping of Event counter (CNTGGIO) has six counters which...
  • Page 19 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Sequential of events DRPRDRE Trip value recorder DRPRDRE Continuous event-logging is useful for monitoring Information about the pre-fault and fault values for the system from an overview perspective and is a currents and voltages are vital for the disturbance complement to specific disturbance recorder evaluation.
  • Page 20 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 the station level. These events are created from any (in%) or an absolute value. The main advantage is available signal in the IED that is connected to the the high accuracy achieved by compensating for Event function (EVENT).
  • Page 21: Human Machine Interface

    ABB IED's and the new IED 670. SPA communication protocol A single glass or plastic port is provided for the ABB SPA protocol. This allows extensions of simple substation automation systems but the main use is IEC07000077 V1 EN for Substation Monitoring Systems SMS.
  • Page 22: Remote Communication

    Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 equipment from different vendors. Disturbance files 15. Remote communication uploading is provided. Analog and binary signal transfer to remote end Three analog and eight binary signals can be DNP3.0 communication protocol exchanged between two IEDs.
  • Page 23: Remote

    Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 the terminal and the battery system. An internal fail Serial and LON communication module SLM, alarm output is available. supports SPA/IEC 60870-5-103, LON and DNP 3.0 The serial and LON communication module (SLM) is Binary input module BIM used for SPA, IEC 60870-5-103, DNP3 and LON The binary input module has 16 optically isolated...
  • Page 24 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 GPS time synchronization module GTM resistor, is available in a single phase unit and a This module includes a GPS receiver used for time three phase unit. Both are mounted on a 1/1 19 synchronization.
  • Page 25 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 xx05000004.vsd IEC05000004 V1 EN Figure 5. Side-by-side mounting Case size 6U, 1/2 x 19” 10.47 8.81 7.92 9.53 9.96 8.10 6U, 3/4 x 19” 10.47 13.23 7.92 9.53 9.96 12.52...
  • Page 26: Connection Diagrams

    Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 17. Connection diagrams Table 1. Designations for 1/2 x 19” casing with 1 TRM slot Module Rear Positions BIM, BOM, SOM, IOM or X31 and X32 etc. to X51 and X52 X301:A, B, C, D LDCM, IRIG-B or RS485...
  • Page 27 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Table 2. Designations for 3/4 x 19” casing with 1 TRM slot Module Rear Positions BIM, BOM, SOM, IOM or X31 and X32 etc. to X101 and X102 X301:A, B, C, D LDCM, IRIG-B or RS485 X302...
  • Page 28 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 1MRK002802-AB-10-670-1.2-PG-ANSI V1 EN Figure 6. Transformer input module (TRM) ■ Indicates high polarity. See table Note that internal polarity can be adjusted by setting of analog input CT neutral direction and/or on SMAI pre- processing function blocks.
  • Page 29 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 1MRK002802-AB-7-670-1.2-PG-ANSI V1 EN Figure 7. Power supply module (PSM)
  • Page 30 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 1MRK002802-AB-11-670-1.2-PG-ANSI V1 EN Figure 8. Binary input module (BIM). Input contacts named XA corresponds to rear position X31, X41, etc. and input contacts named XB to rear position X32, X42, etc. 1MRK002802-AB-12-670-1.2-PG-ANSI V1 EN Figure 9.
  • Page 31 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 1MRK002802-AB-8-670-1.2-PG-ANSI V1 EN Figure 13. IED with basic functionality communication interfaces...
  • Page 32: Remote

    Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 BUS A BUS B 87B-TRIP BFI A 189b 189-OPEN BFI B BFI C 189a 189-CL BFI 3PH 289b 289-OPEN INHIBIT AR 289a 289-CL 3PH TRIP TRM1:10 IN TEST MAN CLOSE TRM1:11 TRM1:1-3...
  • Page 33: Remote

    Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 BUS A 87B-TRIP 189-OPEN 189b BFI A 189-CL 189a BFI B BFI C BFI 3PH TRM1:11 INHIBIT AR TRM1:1-3 3PH TRIP CLOSE TO MAIN 2 PHASE A 152A IN TEST RELAY...
  • Page 34: Technical Data

    Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 18. Technical data General Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the specified requirements Operative range The range of values of a given energizing quantity for which the equipment, under specified...
  • Page 35 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Table 5. TRM - Energizing quantities, rated values and limits for measuring transformer modules Quantity Rated value Nominal range Current = 1 or 5 A (0-1.8) × I at I = 1 A (0-1.6) ×...
  • Page 36 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Auxiliary DC voltage Table 8. PSM - Power supply module Quantity Rated value Nominal range Auxiliary dc voltage, EL (input) EL = (24 - 60) V EL ± 20% EL = (90 - 250) V EL ±...
  • Page 37 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Table 10. BIM - Binary input module with enhanced pulse counting capabilities Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ± 20% 48/60 V RL ±...
  • Page 38 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Table 12. IOM - Binary input/output module contact data (reference standard: IEC 61810-2) Function or quantity Trip and signal relays Fast signal relays (parallel reed relay) Binary outputs Max system voltage 250 V AC, DC 250 V AC, DC...
  • Page 39 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Table 13. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs Function of quantity Static binary output trip Rated voltage 48 - 60 VDC 110 - 250 VDC Number of outputs Impedance open state...
  • Page 40 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Table 14. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs Function of quantity Trip and signal relays Max system voltage 250V AC/DC Number of outputs Test voltage across open contact, 1 min 1000V rms...
  • Page 41 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Influencing factors Table 16. Temperature and humidity influence Parameter Reference value Nominal range Influence Ambient temperature, +20 °C -10 °C to +55 °C 0.02% /°C operate value Relative humidity 10%-90% 10%-90%...
  • Page 42 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Type tests according to standards Table 19. Electromagnetic compatibility Test Type test values Reference standards 1 MHz Oscillatory burst disturbance 2.5 kV IEC 60255-22-1 100 kHz slow damped oscillatory wave immunity 2.5 kV IEC 61000-4-18, Class III test...
  • Page 43 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Table 21. Environmental tests Test Type test value Reference standard Cold test Test Ad for 16 h at -25°C IEC 60068-2-1 Storage test Test Ad for 16 h at -40°C IEC 60068-2-1 Dry heat test Test Bd for 16 h at +70°C...
  • Page 44 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Impedance protection Table 24. Full-scheme distance protection, Mho characteristic ZMHPDIS (21) Function Range or value Accuracy Number of zones with selectable with selectable direction directions Minimum operate current (10–30)% of I Base Positive sequence impedance,...
  • Page 45 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Table 25. Full-scheme distance protection, quadrilateral for earth faults ZMMPDIS (21) Function Range or value Accuracy Number of zones with selectable direction IBase Minimum operate current (10-30)% of Positive sequence reactance (0.50-3000.00) W/phase ±...
  • Page 46 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Table 28. Automatic switch onto fault logic, voltage and current based ZCVPSOF Parameter Range or value Accuracy Operate voltage, detection of dead line (1–100)% of ± 0.5% of V VBase IBase ±...
  • Page 47 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Current protection Table 29. Instantaneous phase overcurrent protection PHPIOC (50) Function Range or value Accuracy Operate current (1-2500)% of lBase ± 1.0% of I at I £ I ±...
  • Page 48 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Table 31. Instantaneous residual overcurrent protection EFPIOC (50N) Function Range or value Accuracy Operate current (1-2500)% of lBase ± 1.0% of I at I £ I ± 1.0% of I at I > I Reset ratio >...
  • Page 49 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Table 32. Four step residual overcurrent protection EF4PTOC (51N/67N) Function Range or value Accuracy lBase Operate current (1-2500)% of ± 1.0% of I at I £ I ±...
  • Page 50 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Table 33. Four step negative sequence overcurrent protection NS4PTOC (46I2) Function Range or value Accuracy lBase Operate value, negative (1-2500)% of ± 1.0% of I at I £ I sequence current, step 1-4 ±...
  • Page 51 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Table 34. Thermal overload protection, one time constant LPTTR (26) Function Range or value Accuracy IBase Reference current (0-400)% of ± 1.0% of I Reference temperature (0-400)°C ±...
  • Page 52 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Table 36. Stub protection STBPTOC (50STB) Function Range or value Accuracy IBase Operating current (1-2500)% of ± 1.0% of I at I £ I ± 1.0% of I at I > I Reset ratio >...
  • Page 53 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Voltage protection Table 39. Two step undervoltage protection UV2PTUV (27) Function Range or value Accuracy Operate voltage, low and high step (1–100)% of VBase ± 0.5% of V Absolute hysteresis (0–100)% of VBase...
  • Page 54 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Table 41. Two step residual overvoltage protection ROV2PTOV (59N) Function Range or value Accuracy VBase Operate voltage, low and high step (1-200)% of ± 0.5% of V at V <...
  • Page 55 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Secondary system supervision Table 43. Current circuit supervision CCSRDIF (87) Function Range or value Accuracy Operate current (5-200)% of I ± 10.0% of I at I £ I ±...
  • Page 56 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Control Table 45. Synchronizing, synchronism check and energizing check SESRSYN (25) Function Range or value Accuracy Phase shift, j (-180 to 180) degrees line Voltage ratio, V (0.40-25.000) % of VBaseBus line...
  • Page 57: Smbrrec

    Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Table 46. Autorecloser SMBRREC (79) Function Range or value Accuracy Number of autoreclosing shots 1 - 5 Autoreclosing open time: shot 1 - t1 1Ph (0.000-60.000) s ±...
  • Page 58 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Scheme communication Table 47. Scheme communication logic for distance or overcurrent protection ZCPSCH (85) Function Range or value Accuracy Scheme type Intertrip Permissive Underreach Permissive Overreach Blocking Co-ordination time for blocking (0.000-60.000) s ±...
  • Page 59: Logic Smpptrc

    Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Logic Table 49. Tripping logic SMPPTRC (94) Function Range or value Accuracy Trip action 3-ph, 1/3-ph, 1/2/3-ph Minimum trip pulse length (0.000-60.000) s ± 0.5% ± 10 ms Timers (0.000-60.000) s ±...
  • Page 60 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Monitoring Table 51. Measurements CVMMXN Function Range or value Accuracy Frequency (0.95-1.05) × f ± 2.0 mHz Connected current (0.2-4.0) × I ± 0.5% of I at I £ I ±...
  • Page 61 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Table 54. Disturbance report DRPRDRE Function Range or value Accuracy Pre-fault time (0.05–9.90) s Post-fault time (0.1–10.0) s Limit time (0.5–10.0) s Maximum number of recordings 100, first in - first out Time tagging resolution 1 ms See table...
  • Page 62 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Table 56. Event list Function Value Buffer capacity Maximum number of events in the list 1000 Resolution 1 ms Accuracy Depending on time synchronizing Table 57. Indications Function Value Buffer capacity...
  • Page 63 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Metering Table 61. Pulse counter PCGGIO Function Setting range Accuracy Input frequency See Binary Input Module (BIM) Cycle time for report of counter (1–3600) s value Table 62. Energy metering ETPMMTR Function Range or value Accuracy...
  • Page 64 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Station communication Table 63. IEC 61850-8-1 communication protocol Function Value Protocol IEC 61850-8-1 Communication speed for the IEDs 100BASE-FX Table 64. LON communication protocol Function Value Protocol Communication speed 1.25 Mbit/s Table 65.
  • Page 65 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Table 68. SLM – SPA/IEC 60870-5-103/DNP3 port Quantity Range or value Optical connector Glass fiber: type ST Plastic fiber: type HFBR snap-in Fiber, optical budget Glass fiber: 11 dB (3000ft/1000 m typically *) Plastic fiber: 7 dB (80ft/25 m typically *) diameter Glass fiber: 62.5/125 mm...
  • Page 66: Remote

    Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Remote communication Table 72. Line data communication module Characteristic Range or value Type of LDCM Short range (SR) Medium range (MR) Long range (LR) Type of fiber Graded-index Singlemode 9/125 µm Singlemode 9/125 µm...
  • Page 67 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Hardware Table 73. Case Material Steel sheet Front plate Steel sheet profile with cut-out for HMI Surface treatment Aluzink preplated steel Finish Light grey (RAL 7035) Table 74. Water and dust protection level according to IEC 60529 Front IP40 (IP54 with sealing strip) Rear, sides, top and...
  • Page 68 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Basic IED functions Table 78. Self supervision with internal event list Data Value Recording manner Continuous, event controlled List size 1000 events, first in-first out Table 79. Time synchronization, time tagging Function Value Time tagging resolution, events and sampled measurement values...
  • Page 69 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Table 82. IRIG-B Quantity Rated value Number of channels IRIG-B Number of channels PPS Electrical connector: Electrical connector IRIG-B Pulse-width modulated 5 Vpp Amplitude modulated – low level 1-3 Vpp –...
  • Page 70 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Inverse characteristic Table 83. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: td = (0.05-999) in steps of 0.01 unless otherwise stated æ ö ç...
  • Page 71 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Table 84. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: td = (0.05-999) in steps of 0.01 æ ö ç ÷ × ç ÷ è...
  • Page 72 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Table 85. RI and RD type inverse time characteristics Function Range or value Accuracy RI type inverse characteristic td = (0.05-999) in steps of 0.01 IEC 60255-3, class 5 + 40 ms ×...
  • Page 73 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Table 86. Inverse time characteristics for overvoltage protection Function Range or value Accuracy Type A curve: td = (0.05-1.10) in steps of 0.01 unless Class 5 +40 ms otherwise stated æ...
  • Page 74 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Table 87. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: td = (0.05-1.10) in steps of 0.01 unless Class 5 +40 ms otherwise stated æ...
  • Page 75 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Table 88. Inverse time characteristics for residual overvoltage protection Function Range or value Accuracy Type A curve: td = (0.05-1.10) in steps Class 5 +40 ms of 0.01 æ...
  • Page 76: Ordering

    Version no Selection for position #1. Configuration alternatives Notes and Rules Multi breaker, 1-phase tripping ACT configuration ABB standard configuration Selection for position #2. Software options Notes and Rules No option All fields in the ordering form do not need to be filled in...
  • Page 77 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Casing Notes and Rules 1/2 x 19" case 3/4 x 19" case 1TRM slot Selection for position #5 Mounting details with IP40 of protection from the front Notes and Rules No mounting kit included 19"...
  • Page 78 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Binary input/output module, mA and time synchronization boards. Notes and Rules Make BIM with 50 mA inrush current the primary choice. BIM with 50 mA inrush current fulfill additional standards. As a consequence the EMC withstand capability is further increased.
  • Page 79: Remote

    Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Remote end communication, DNP serial comm. and time Notes and Rules synchronization modules Slot position (rear view) Available slots in 1/2 case with 1 TRM █ █ █...
  • Page 80: Remote

    Please refer to Section 001-BEN and 1MRK 001024-CA. Please refer to "Related documents" for reference to the website: www.abb.com/substationautomation corresponding documents. for detailed information. Test switches type RTXP 24 is ordered separately. Please refer to Section "Related documents"...
  • Page 81 Line distance protection REL670 ANSI 1MRK 506 317-BUS A Pre-configured Product version: 1.2 Side-by-side mounting kit Quantity: 1MRK 002 420-Z Configuration and monitoring tools Front connection cable between LCD-HMI and PC Quantity: 1MRK 001 665-CA LED Label special paper A4, 1 pc Quantity: 1MRK 002 038-CA LED Label special paper Letter, 1 pc...
  • Page 82 670 series SPA and signal list 1MRK 500 092-WUS IEC 61850 Data objects list for 670 series 1MRK 500 091-WUS Engineering manual 670 series 1MRK 511 256-UUS Communication set-up for Relion 670 series 1MRK 505 260-UEN More information can be found on www.abb.com/substationautomation.
  • Page 84 ABB Inc. 3450 Harvester Road Burlington, ON L7N 3W5, Canada Phone Toll Free: 1-800-HELP-365, menu option #8 ABB Mexico S.A. de C.V. Paseo de las Americas No. 31 Lomas Verdes 3a secc. 53125, Naucalpan, Estado De Mexico, MEXICO Phone (+1) 440-585-7804, menu...