  • Page 1 ® Relion 670 series Phasor measurement unit RES670 Pre-configured Product Guide...
  • Page 2: Table Of Contents

    10. Logic................14 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. © Copyright 2012 ABB.
  • Page 3 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Issued: June 2012 Revision: -...
  • Page 4: Application

    Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 1. Application WAN / LAN Events printer Printer satellite Gateway Substation LAN C37.118 Station PDC RES670 RES670 IEC11000408_1_en.eps GUID-13F439FC-6AB6-4ED0-A629-EBC8F984B447 V1 EN Figure 1. PMUs in a substation RES 670 is a Phasor Measurement Unit that The data concentrator is usually a mass storage provides power system AC voltages and currents with capacity for about one week of data in a...
  • Page 5 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 voltage of the busbar and three 3-phase currents Description of A20 configuration of bays 1 to 3. In addition, there are Binary Inputs RES670 A20 configuration is applicable for a and protection function triggers which are typical single busbar single breaker arrangement reported through PMU.
  • Page 6 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 on B20 are Over Voltage, Under Voltage, Over Frequency, Under Frequency, and Rate of Change of Frequency. RES670 - Double Busbar, Six bays, 24AI (18I+6U) df/dt df/dt SA PFRC SA PFRC S XSWI f>...
  • Page 7: Available Functions

    Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 2. Available functions Wide area measurement functions IEC 61850 ANSI Function description Phasor measurement unit PMUCONF Configuration parameters for IEEE1344 and C37.118 protocol PMUREPORT Protocol reporting via IEEE1344 and C37.118 Back-up protection functions IEC 61850 ANSI...
  • Page 8 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Control and monitoring functions IEC 61850 ANSI Function description Phasor measurement unit Control QCBAY Apparatus control Local Handling of LRswitch positions Remote LocRem LHMI control of PSTO Control SLGGIO Logic rotating switch for function selection and LHMI presentation VSGGIO...
  • Page 9 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 IEC 61850 ANSI Function description Phasor measurement unit SPGGIO IEC61850 generic communication I/O functions SP16GGIO IEC61850 generic communication I/O functions 16 inputs MVGGIO IEC61850 generic communication I/O functions BSStart Logical signal status report Report...
  • Page 10: Wide Area Measurement System

    Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Basic IED functions IEC 61850 Function description Basic functions included in all products IntErrorSig Self supervision with internal event list TIME Time and synchronization error TimeSynch Time synchronization ActiveGroup Parameter setting groups Test...
  • Page 11: Current Protection

    Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 All IEC and ANSI time-delayed characteristics are Protocol reporting via IEEE 1344 and C37.118 available together with an optional user defined PMUREPORT characteristic. The phasor measurement reporting block moves the phasor calculations into a C37.118 frame EF4PTOC can be set directional or non- which contains data about PMU configuration,...
  • Page 12: Voltage Protection

    Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 communication or voltage transformer circuit UV2PTUV has two voltage steps, each with failure. inverse or definite time delay. Directional operation can be combined together Two step overvoltage protection OV2PTOV with corresponding communication logic in Overvoltages may occur in the power system permissive or blocking teleprotection scheme.
  • Page 13: Multipurpose Protection

    Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 The operation is based on positive sequence It must be remembered that a blocking of voltage measurement and requires two phase- protection functions at an occurrence of open CT phase or three phase-neutral voltages to be circuit will mean that the situation will remain and connected.
  • Page 14: Control

    Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 A criterion based on delta current and delta other means, such as binary inputs and SPGGIO voltage measurements can be added to the fuse function blocks. The commands can be pulsed or failure supervision function in order to detect a steady.
  • Page 15: Monitoring

    Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 • PULSETIMER function block can be used, for • measured voltages, currents, frequency, example, for pulse extensions or limiting of active, reactive and apparent power and operation of outputs, settable pulse time. power factor •...
  • Page 16 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 conditions, recording times, and large storage short term (for example corrective actions) and in capacity. the long term (for example functional analysis). A disturbance is defined as an activation of an The event recorder logs all selected binary input input to the AxRADR or BxRBDR function blocks, signals connected to the Disturbance report...
  • Page 17: Metering

    Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 seconds of data before the trigger instant can be 12. Metering saved in the disturbance file. Pulse counter logic PCGGIO Pulse counter (PCGGIO) function counts The disturbance recorder information for up to externally generated binary pulses, for instance 100 disturbances are saved in the IED and the pulses coming from an external energy meter, for...
  • Page 18: Station Communication

    Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 label. All LEDs are configurable from Multiple command and transmit PCM600. When 670 IED's are used in Substation • Liquid crystal display (LCD). Automation systems with LON, SPA or •...
  • Page 19 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 mA input module MIM with a dedicated Master and the rest are slaves. The milli-ampere input module is used to interface No special control signal is needed in this case. transducer signals in the –20 to +20 mA range GPS time synchronization module GTM from for example OLTC position, temperature or...
  • Page 20 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Case size 6U, 1/1 x 19” 265.9 448.1 201.1 242.1 252.9 430.3 (mm) See ordering for details about available mounting Mounting alternatives The following mounting alternatives are available alternatives.
  • Page 21: Connection Diagrams

    Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 17. Connection diagrams Table 1. Designations for 1/1 x 19” casing with 2 TRM slots Module Rear Positions BIM, BOM, SOM, X31 and X32 etc. to X131 IOM or MIM and X132 X301:A, B, C, D LDCM, IRIG-B or...
  • Page 22 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 1MRK002801-AC-10-670-1.2-PG V1 EN Figure 6. Transformer input module (TRM) ■ Indicates high polarity CT/VT-input designation according to figure AI01 AI02 AI03 AI04 AI05 AI06 AI07 AI08 AI09 AI10 AI11 AI12 9I+3U,...
  • Page 23 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 1MRK002801-AC-15-670-1.2-PG V1 EN Figure 8. mA input module (MIM) 1MRK002801-AC-11-670-1.2-PG V1 EN Figure 7. Binary input module (BIM). Input contacts named XA corresponds to rear position X31, X41, and so on, and input contacts named XB to rear position X32, X42, and so on.
  • Page 24 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 1MRK002801-AC-7-670-1.2-PG V1 EN Figure 10. Power supply module (PSM) 1MRK002801-AC-12-670-1.2-PG V1 EN Figure 11. Binary output module (BOM). Output contacts named XA corresponds to rear position X31, X41, and so on, and output contacts named XB to rear position X32, X42, and so on.
  • Page 25 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 1MRK002801-AC-13-670-1.2-PG V1 EN Figure 12. Static output module (SOM) 1MRK002801-AC-14-670-1.2-PG V1 EN Figure 13. Binary in/out module (IOM). Input contacts named XA corresponds to rear position X31, X41, and so on, and output contacts named XB to rear position X32, X42, and so on.
  • Page 26: Technical Data

    Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 18. Technical data General Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the specified requirements Operative range The range of values of a given energizing quantity for which the equipment, under specified...
  • Page 27 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Table 3. TRM - Energizing quantities, rated values and limits for measuring transformer modules Quantity Rated value Nominal range Current = 1 or 5 A (0-1.8) × I at I = 1 A (0-1.6) ×...
  • Page 28 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Auxiliary DC voltage Table 6. PSM - Power supply module Quantity Rated value Nominal range Auxiliary dc voltage, EL (input) EL = (24 - 60) V EL ± 20% EL = (90 - 250) V EL ±...
  • Page 29 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Table 9. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs Function of quantity Static binary output trip Rated voltage 48 - 60 VDC 110 - 250 VDC Number of outputs Impedance open state ~300 kΩ...
  • Page 30 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Table 11. BOM - Binary output module contact data (reference standard: IEC 61810-2) Function or quantity Trip and Signal relays Binary outputs Max system voltage 250 V AC, DC Test voltage across open contact, 1 min 1000 V rms Current carrying capacity...
  • Page 31 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Table 14. Frequency influence (reference standard: IEC 60255–1) Dependence on Within nominal range Influence Frequency dependence, operate value ± 2.5 Hz for 50 Hz ± 1.0% / Hz ±...
  • Page 32 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Table 16. Insulation Test Type test values Reference standard Dielectric test 2.0 kV AC, 1 min. IEC 60255-5 Impulse voltage test 5 kV, 1.2/50 ms, 0.5 J Insulation resistance >100 MW at 500 VDC Table 17.
  • Page 33 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Wide area measurement system Table 20. Protocol reporting via IEEE 1344 and C37.118 PMUREPORT Influencing quantity Range Accuracy Signal frequency ± 0.1 x f ≤ 1.0% TVE Signal magnitude: Voltage phasor (0.1–1.2) x U Current phasor...
  • Page 34 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Current protection Table 21. Four step phase overcurrent protection OC4PTOC Function Setting range Accuracy lBase Operate current (1-2500)% of ± 1.0% of I at I ≤ I ± 1.0% of I at I > I Reset ratio >...
  • Page 35 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Table 22. Four step residual overcurrent protection EF4PTOC Function Range or value Accuracy Operate current (1-2500)% of lBase ± 1.0% of I at I £ I ± 1.0% of I at I > I Reset ratio >...
  • Page 36 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Table 23. Four step negative sequence overcurrent protection NS4PTOC Function Range or value Accuracy Operate value, negative (1-2500)% of lBase ± 1.0% of I at I £ I sequence current, step 1-4 ±...
  • Page 37 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Table 24. Sensitive directional residual overcurrent and power protection SDEPSDE Function Range or value Accuracy Operate level for 3I ·cosj (0.25-200.00)% of lBase ± 1.0% of I at I £ I directional residual overcurrent ±...
  • Page 38 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Table 25. Thermal overload protection, one time constant LPTTR Function Range or value Accuracy Reference current (0-400)% of IBase ± 1.0% of I Reference temperature ± 1.0°C, ±2°F Operate time: Time constant t = (0–1000) minutes IEC 60255-8, ±5% + 200 ms...
  • Page 39 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Voltage protection Table 26. Two step undervoltage protection UV2PTUV Function Range or value Accuracy UBase Operate voltage, low and high step (1–100)% of ± 0.5% of U UBase Absolute hysteresis (0–100)% of ±...
  • Page 40 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Frequency protection Table 28. Underfrequency protection SAPTUF Function Range or value Accuracy Operate value, start function (35.00-75.00) Hz ± 2.0 mHz Operate time, start function 100 ms typically Reset time, start function 100 ms typically Operate time, definite time function...
  • Page 41 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Multipurpose protection Table 31. General current and voltage protection CVGAPC Function Range or value Accuracy Measuring current input phase1, phase2, phase3, PosSeq, NegSeq, 3*ZeroSeq, MaxPh, MinPh, UnbalancePh, phase1-phase2, phase2- phase3, phase3-phase1, MaxPh-Ph, MinPh-Ph, UnbalancePh-Ph Base current...
  • Page 42 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Table 31. General current and voltage protection CVGAPC , continued Function Range or value Accuracy Reset time start undervoltage 25 ms typically at 0 to 2 x U High and low voltage limit, voltage (1.0 - 200.0)% of UBase ±...
  • Page 43 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Secondary system supervision Table 32. Current circuit supervision CCSRDIF Function Range or value Accuracy Operate current (5-200)% of I ± 10.0% of I at I £ I ± 10.0% of I at I > I Block current (5-500)% of I ±...
  • Page 44 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Logic Table 34. Tripping logic SMPPTRC Function Range or value Accuracy Trip action 3-ph, 1/3-ph, 1/2/3-ph Timers (0.000-60.000) s ± 0.5% ± 10 ms Table 35. Configurable logic blocks Logic block Quantity with cycle time Range or value...
  • Page 45 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Monitoring Table 36. Phase current measurement CMMXU Function Range or value Accuracy Current (0.1-4.0) × I ± 0.2% of I at I ≤ 0.5 × I ± 0.2% of I at I > 0.5 × I Phase angle (0.1–4.0) x I ±...
  • Page 46 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Table 40. Voltage sequence measurement VMSQI Function Range or value Accuracy Voltage positive sequence, U1 (10 to 300) V ± 0.3% of U at U ≤ 50 V ±...
  • Page 47 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Table 43. Disturbance report Function Range or value Accuracy Pre-fault time (0.05–9.90) s Post-fault time (0.1–10.0) s Limit time (0.5–10.0) s Maximum number of recordings 100, first in - first out Time tagging resolution 1 ms See table...
  • Page 48 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Table 46. Event recorder Function Value Buffer capacity Maximum number of events in disturbance report Maximum number of disturbance reports Resolution 1 ms Accuracy Depending on time synchronizing Table 47.
  • Page 49 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Metering Table 49. Pulse counter PCGGIO Function Setting range Accuracy Input frequency See Binary Input Module (BIM) Cycle time for report of counter (1–3600) s value Table 50. Energy metering ETPMMTR Function Range or value Accuracy...
  • Page 50 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Station communication Table 51. IEC 61850-8-1 communication protocol Function Value Protocol IEC 61850-8-1 Communication speed for the IEDs 100BASE-FX Table 52. Galvanic RS485 communication module Quantity Range or value Communication speed 2400–19200 bauds External connectors...
  • Page 51 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Hardware Table 54. Case Material Steel sheet Front plate Steel sheet profile with cut-out for HMI Surface treatment Aluzink preplated steel Finish Light grey (RAL 7035) Table 55. Water and dust protection level according to IEC 60529 Front IP40 (IP54 with sealing strip) Rear, sides, top and...
  • Page 52 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Basic IED functions Table 59. Self supervision with internal event list Data Value Recording manner Continuous, event controlled List size 1000 events, first in-first out Table 60. Time synchronization, time tagging Function Value Time tagging resolution, events and sampled measurement values...
  • Page 53 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Table 63. IRIG-B Quantity Rated value Number of channels IRIG-B Number of channels PPS Electrical connector: Electrical connector IRIG-B Pulse-width modulated 5 Vpp Amplitude modulated – low level 1-3 Vpp –...
  • Page 54 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Inverse characteristic Table 64. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: k = (0.05-999) in steps of 0.01 æ ö ç ÷ × ç ÷...
  • Page 55 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Table 65. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: k = (0.05-999) in steps of 0.01 æ ö ç ÷ × ç ÷ è ø...
  • Page 56 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Table 66. RI and RD type inverse time characteristics Function Range or value Accuracy RI type inverse characteristic k = (0.05-999) in steps of 0.01 IEC 60255-151, 5% + 40 ×...
  • Page 57 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Table 68. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 5% +40 ms æ ö <...
  • Page 58: Ordering

    Selection for position #1. Configuration alternatives Notes and Rules 3Ix1U phasors 6Ix2U phasors ACT configuration ABB standard configuration Selection for position #2. Software options Notes and Rules No option All fields in the ordering form do not need to be filled in...
  • Page 59 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Mounting details with IP40 of protection from the front Notes and Rules No mounting kit included 19" rack mounting kit for 1/1 x 19" case Wall mounting kit Note: Wall mounting not recommended with communication modules with...
  • Page 60 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Binary input/output module, mA Notes and Rules and time synchronization boards. Note: 1BIM and 1 BOM included. For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used. Slot position (rear view) Note: Max 11 positions in 1/1 rack with 2 TRM...
  • Page 61 512 001-BEN and 1MRK 001024-CA. Please separately. Please refer to Section "Related refer to the website: documents" for reference to corresponding www.abb.com/substationautomation for detailed documents. information. RHGS 6 Case or RHGS 12 Case with mounted 1 TRM Single busbar/2 TRMs Double busbar with...
  • Page 62 Phasor measurement unit RES670 1MRK 511 266-BEN - Pre-configured Product version: 1.2 Manuals Note: One (1) IED Connect CD containing user documentation (Operator’s manual, Technical reference manual, Installation and commissioning manual, Application manual and Getting started guide), Connectivity packages and LED label template is always included for each IED. Rule: Specify additional quantity of IED Connect CD requested .
  • Page 63 670 series SPA and signal list 1MRK 500 092-WEN IEC 61850 Data objects list for 670 series 1MRK 500 091-WEN Engineering manual 670 series 1MRK 511 256-UEN Communication set-up for Relion 670 series 1MRK 505 260-UEN More information can be found on www.abb.com/substationautomation.
  • Page 65 Contact us ABB AB Substation Automation Products SE-721 59 Västerås, Sweden Phone +46 (0) 21 32 50 00 +46 (0) 21 14 69 18 www.abb.com/substationautomation...