  • Page 1 ® Relion 670 SERIES Busbar protection REB670 Version 2.2 Product guide...
  • Page 2 (eay@cryptsoft.com) and Tim Hudson (tjh@cryptsoft.com). Trademarks ABB is a registered trademark of ABB Asea Brown Boveri Ltd. Manufactured by/for a Hitachi Power Grids company. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.
  • Page 3 Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not to be deemed as a statement of guaranteed properties. All persons responsible for applying the equipment addressed in this manual must satisfy themselves that each intended application is suitable and acceptable, including that any applicable safety or other operational requirements are complied with.
  • Page 4 Conformity This product complies with the directive of the Council of the European Communities on the approximation of the laws of the Member States relating to electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by Hitachi Power Grids in accordance with the product standard EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
  • Page 5: Table Of Contents

    Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Contents 1. Document revision history..........6 14. Metering..............43 2. Application..............7 15. Human machine interface.......... 44 3. Available functions............15 16. Basic IED functions............ 44 4. Differential protection...........28 17. Ethernet..............44 5. Zone selection............. 29 18.
  • Page 6: Document Revision History

    Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Issued: June 2021 Revision: P 1. Document revision history GUID-34B323E4-1319-4D42-80CE-29B0F2D36E2C v5 Table 1. Document revision history Document Date Product version History revision Document not released 2017-07 2.2.0 First release for product version 2.2 2017-10 2.2.1 Ethernet ports with RJ45 connector added.
  • Page 7: Application

    Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 provided with a restraint feature. The minimum pick-up value for the differential current is set to give a suitable 2. Application sensitivity for all internal faults. The pick-up setting for the SEMOD121007-5 v9 The Intelligent Electronic Device (IED) is designed for the fault current must be less than 80% of the lowest fault...
  • Page 8 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Sensitive differential protection Operate region Differential protection operation characteristic DiffOperLevel SensIinBlock SensOperLevel s=0.53 [Primary Amps] IEC06000142-2-en.vsdx IEC06000142 V2 EN-US Figure 1. IED operating characteristic Integrated overall check zone feature, independent from any Advanced Zone Selection logic accompanied by optionally disconnector position, is available.
  • Page 9 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 phase IED with external auxiliary summation current Description of pre-configured packages transformers. GUID-52088734-B524-4ACF-8F1F-7CCD9D9BFBFA v2 There are five pre-configured variants of REB670. They are describe in the following Table: The IED can be used in applications with IEC/UCA 61850-9-2LE process bus with up to eight merging units Table 2.
  • Page 10 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Configuration X01 Configuration X03 SEMOD129275-116 v6 SEMOD129275-124 v5 This configuration includes only busbar protection for simple This configuration includes BBP with breaker failure stations layouts (in other words, one-and-a-half breaker, protection CCRBRF, end fault protection and overcurrent double breaker or single breaker stations).
  • Page 11 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Table 4. Typical solutions for stations with two busbar sections connected with bus-sectionalizing disconnector Version of REB670 pre-configured IED Total Number of feeders in both busbar Number of REB670 IEDs required for the sections scheme 3PH;...
  • Page 12 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 QB20 xx06000015.vsd IEC06000015 V1 EN-US Figure 6. Example of double bus-single breaker station with transfer bus QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 xx06000016.vsd IEC06000016 V1 EN-US...
  • Page 13 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 IEC11000240-1-en.vsd IEC11000240 V1 EN-US Figure 8. Example of one-and-a-half breaker station Table 7. Typical solutions for one-and-half circuit breaker stations when CBF for middle breaker is not required Version of REB670 pre-configured IED Number of diameters in the station Number of REB670 IEDs required for the scheme...
  • Page 14 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 QB12 QB11 QB41 QB21 QB42 QB22 QB31 QB32 xx06000019.vsd IEC06000019 V1 EN-US Figure 10. Example of mesh or ring bus station Note that customized REB670 is delivered without any configuration. Thus the complete IED engineering shall be done by the customer or its system integrator.
  • Page 15: Available Functions

    Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 3. Available functions GUID-F5776DD1-BD04-4872-BB89-A0412B4B5CC3 v1 The following tables list all the functions available in the IED. Those functions that are not exposed to the user or do not need to be configured are not described in this manual.
  • Page 16 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Back-up protection functions GUID-A8D0852F-807F-4442-8730-E44808E194F0 v17 IEC 61850 or ANSI Function description Busbar function name REB670 (Customized) Current protection OC4PTOC Directional phase overcurrent protection, 4-C06 8-C07 51_67 four steps PH4SPTOC Single phase overcurrent protection, four 0-24 steps EF4PTOC...
  • Page 17 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Control and monitoring functions GUID-E3777F16-0B76-4157-A3BF-0B6B978863DE v21 IEC 61850 or ANSI Function description Busbar function name REB670 (Customized) Control SESRSYN Synchrocheck, energizing check and synchronizing SMBRREC Autorecloser 2-H05 2-H05 2-H05 2-H05 2-H05 APC30 Control functionality for up to 6 bays, max 30 objects (6CBs), including interlocking (see...
  • Page 18 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 IEC 61850 or ANSI Function description Busbar function name REB670 (Customized) DELVSPVC 7V_78V Voltage delta supervision, 2 phase DELISPVC Current delta supervision, 2 phase DELSPVC Real delta supervision, real Logic TMAGAPC Trip matrix logic ALMCALH Logic for group alarm...
  • Page 19 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 IEC 61850 or ANSI Function description Busbar function name REB670 (Customized) TEIGAPC Elapsed time integrator with limit transgression and overflow supervision INTCOMP Comparator for integer inputs REALCOMP Comparator for real inputs HOLDMINMAX Hold minimum and maximum of input INT_REAL...
  • Page 20 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 IEC 61850 or ANSI Function description Busbar function name REB670 (Customized) Monitoring CVMMXN Power system measurement CMMXU Current measurement VMMXU Voltage measurement phase-phase CMSQI Current sequence measurement VMSQI Voltage sequence measurement VNMMXU Voltage measurement phase-earth AISVBAS...
  • Page 21 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 IEC 61850 or ANSI Function description Busbar function name REB670 (Customized) I103USRDEF Status for user defined signals for IEC 60870-5-103 L4UFCNT Event counter with limit supervision TEILGAPC Running hour meter CHMMHAI ITHD Current harmonic monitoring, 3 phase 3-M23...
  • Page 22 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Table 11. Number of function instances in APC30 Function name Function description Total number of instances SCILO Interlocking BB_ES A1A2_BS A1A2_DC ABC_BC BH_CONN BH_LINE_A BH_LINE_B DB_BUS_A DB_BUS_B DB_LINE ABC_LINE AB_TRAFO SCSWI Switch controller SXSWI Circuit switch...
  • Page 23 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Table 13. Total number of instances for extended logic package Extended configurable logic block Total number of instances GATE PULSETIMER RSMEMORY SLGAPC SRMEMORY TIMERSET VSGAPC Hitachi Power Grids © 2017 - 2021 Hitachi Power Grids. All rights reserved...
  • Page 24 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Communication GUID-5F144B53-B9A7-4173-80CF-CD4C84579CB5 v19 IEC 61850 or ANSI Function description Busbar function name REB670 (Customized) Station communication LONSPA, SPA SPA communication protocol LON communication protocol HORZCOMM Network variables via LON PROTOCOL Operation selection between SPA and IEC60870-5-103 for SLM RS485PROT Operation selection for RS485...
  • Page 25 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 IEC 61850 or ANSI Function description Busbar function name REB670 (Customized) OPTICAL103 IEC 60870-5-103 Optical serial communication RS485103 IEC 60870-5-103 serial communication for RS485 AGSAL Generic security application component LD0LLN0 IEC 61850 LD0 LLN0 SYSLLN0 IEC 61850 SYS LLN0 LPHD...
  • Page 26 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 IEC 61850 or ANSI Function description Busbar function name REB670 (Customized) BinSignTrans1_1 Binary signal transfer, transmit 3/3/6 3/3/6 3/3/6 3/3/6 3/3/6 3/3/6 BinSignTrans1_2 BinSignTransm2 BSR2M_305 Binary signal transfer, 2Mbit receive BSR2M_312 BSR2M_322 BSR2M_306 BSR2M_313...
  • Page 27 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Basic IED functions GUID-C8F0E5D2-E305-4184-9627-F6B5864216CA v15 Table 14. Basic IED functions IEC 61850 or function Description name INTERRSIG Self supervision with internal event list SELFSUPEVLST TIMESYNCHGEN Time synchronization module BININPUT, SYNCHCAN, Time synchronization SYNCHGPS, SYNCHCMPPS, SYNCHLON,...
  • Page 28: Differential Protection

    Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Table 14. Basic IED functions, continued IEC 61850 or function Description name SAFEFILECOPY Safe file copy function ALTMS Time master supervision ALTIM Time management CAMCONFIG Central account management configuration CAMSTATUS Central account management status TOOLINF Tools information COMSTATUS...
  • Page 29: Zone Selection

    Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 by a binary signal (e.g. start signal from external open delta circuits have been found and associated error has been VT overvoltage relay or external power transformer neutral corrected a manual reset must be given to the IED. This can point overcurrent relay).
  • Page 30 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 primary switching object will be determined. The dedicated Regardless which scheme is used the time-delayed function block for each primary switching object is available disconnector/circuit breaker status supervision alarm is in order to determine the status of the object primary available (that is, 00 or 11 auxiliary contact status).
  • Page 31 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 logical value is zero (that is, CntrlExcludes). This option is • Trip only the bay circuit breaker (used for integrated OC typically used when only normally closed auxiliary protection tripping) contacts from the busbar disconnector are available to the •...
  • Page 32: Current Protection

    Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 EF4PTOC has an inverse or definite time delay independent for each step. 6. Current protection All IEC and ANSI time-delayed characteristics are available Directional phase overcurrent protection, four steps together with an optional user-defined characteristic. OC4PTOC M12846-3 v18 Directional phase overcurrent protection, four steps...
  • Page 33: Voltage Protection

    Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 temperatures are reached. If the temperature continues to The CCSRBRF function can be programmed to give a retrip increase to the trip value, the protection initiates a trip of the to its own breaker to avoid unnecessary tripping of protected transformer.
  • Page 34: Frequency Protection

    Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 OV2PTOV has a high reset ratio to allow settings close to Overfrequency occurs because of sudden load drops or system service voltage. shunt faults in the power network. Close to the generating plant, generator governor problems can also cause over Residual overvoltage protection, two steps frequency.
  • Page 35: Control

    Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 The zero sequence detection is recommended for IEDs Delta supervision of real input DELSPVC used in directly or low impedance earthed networks. It is GUID-8FAD2CCF-091F-4CDB-8ABF-1BDC874A8403 v2 Delta supervision functions are used to quickly detect based on the zero sequence measuring quantities.
  • Page 36 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 breaker to reclose first and the second will only close if the For easy and safe implementation of the interlocking fault proved to be transient. function, the IED is delivered with standardized and tested software interlocking modules containing logic for the Each auto reclosing function can be configured to co- interlocking conditions.
  • Page 37: Logic

    Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 this way, simple commands can be sent directly to the IED GOOSE function block to receive a switching device outputs, without confirmation. Confirmation (status) of the GOOSEXLNRCV result of the commands is supposed to be achieved by other GUID-5AC7DE11-CB95-4565-A8AE-FB23D59FD717 v1 The GOOSE XLN Receive component is used to collect means, such as binary inputs and SPGAPC function blocks.
  • Page 38 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 The logic blocks are available as a part of an extension SP_OUT output. TIME input is copied to time part of logic package. The list below is a summary of the function SP_OUT output.
  • Page 39 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Boolean, integer, floating point, string types of signals are Comparator for integer inputs INTCOMP available. GUID-A93564FA-0017-4939-A9C1-095DA0FD9832 v1 The function gives the possibility to monitor the level of integer values in the system relative to each other or to a One FXDSIGN function block is included in all IEDs.
  • Page 40: Monitoring

    Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 • measured voltages, currents, frequency, active, reactive Absolute value ABS and apparent power and power factor GUID-A5BF20EF-F04B-4546-B6D0-C1343A56ED72 v1 The absolute value (ABS) function gives the absolute value • measured analog values from merging units of the input.
  • Page 41 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Every disturbance report recording is saved in the IED in Trip value recorder DRPRDRE the standard COMTRADE format. In the COMTRADE1999 M12128-3 v7 Information about the pre-fault and fault values for currents format it is saved as a header file HDR, a configuration file and voltages are vital for the disturbance evaluation.
  • Page 42 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Generic communication function for measured Event counter with limit supervison L4UFCNT GUID-13157EAB-1686-4D2E-85DF-EC89768F3572 v6 values MVGAPC The Limit counter (L4UFCNT) provides a settable counter SEMOD55872-5 v10 Generic communication function for measured values with four independent limits where the number of positive (MVGAPC) function is used to send the instantaneous value and/or negative flanks on the input signal are counted...
  • Page 43: Metering

    Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 to the fundamental signal amplitude which indicates the Function for energy calculation and demand handling voltage signal quality factor. ETPMMTR GUID-6898E29B-DA70-421C-837C-1BBED8C63A7A v3 Power system measurement (CVMMXN) can be used to Additionally, the function is used to calculate the numerical measure active as well as reactive power values.
  • Page 44: Human Machine Interface

    Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 The IED supports SNTPv4 (RFC2030). 15. Human machine interface Local HMI M11345-3 v13 AMU0600442 v15 Precision time protocol PTP PTP according to IEEE 1588-2008 and specifically its profile IEC/IEEE 61850-9-3 for power utility automation is a synchronization method that can be used to maintain a common time within a station.
  • Page 45: Station Communication

    Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 For RSTP, the frame error rate on an individual link cannot be extrapolated accurately to that of which is received by the IED. Hence, the frame error rate on link A (LCCH.FerCh) and the frame error Default gateway rate on link B (LCCH.RedFerCh) cannot be calculated and are 0 always.
  • Page 46 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 The front port is only intended for LON communication protocol PCM600 communication, maintenance, SEMOD120140-5 v4 Existing stations with Hitachi Power Grids station bus LON training and test purposes due to risk of can be extended with use of the optical LON interface interference during normal operation.
  • Page 47: Remote Communication

    Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 correspondent signal present in the configuration. For IED commands with position and select for IEC example: 68_TRGEN represents the General Trip of the 60870-5-103 I103POSCMD device and must be connected to the general trip signal GUID-658C58A6-8B78-4740-BA83-195990308953 v1 I103POSCMD has double-point position indicators that are SMPPTRC_TRIP or equivalent.
  • Page 48: Hardware Description

    Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 configured to work in either analog mode or binary mode. In used with the pulse counter function. The binary inputs are analog mode, the IED can send and receive up to 3 analog freely programmable and can be used for the input of logical signals and up to 8 binary signals.
  • Page 49 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Short range LDCM (820 nm multi mode fiber), Layout and dimensions IP14539-1 v1 Dimensions Medium range (1310 nm single mode fiber) IP14826-1 v1 M15243-4 v7 and Long range (1550 nm single mode fiber) . Galvanic RS485 serial communication module SEMOD158664-5 v3 The Galvanic RS485 communication module (RS485) is...
  • Page 50 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 M15243-12 v11 IEC06000182-2-en.vsd IEC06000182 V2 EN-US Figure 17. A 1/2 x 19” size IED side-by-side with RHGS6. Table 17. Case dimensions Case size (mm)/ (inches) 6U, 1/2 x 19” 265.9/ 223.7/ 247.5/ 255.0/ 205.8/...
  • Page 51: Connection Diagrams

    10289889-INC-21-2985 Connection diagram, REB670 2.2, A31X01 certificate issued by DNV GL 1MRK002807-BK IEC 61850 Ed1 level B1 1KHL050134 certificate issued by Hitachi ABB Connection diagram, REB670 2.2, A31X02 Power Grids, SVC Baden 1MRK002807-BL IEC 62439-3 Ed3 certificate 10257149-INC 21-2619rev1 Connection diagram, REB670 2.2, A31X03...
  • Page 52: Technical Data

    Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 23. Technical data General M10993-1 v4 IP11376-1 v3 Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the specified requirements Operative range The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to perform its...
  • Page 53 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Energizing quantities, rated values and limits Analog inputs M16988-1 v11 IP15842-1 v1 Table 18. TRM - Energizing quantities, rated values and limits for protection transformer Description Value Frequency Rated frequency f 50/60 Hz Operating range ±...
  • Page 54 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Table 19. TRM - Energizing quantities, rated values and limits for measuring transformer Description Value Frequency Rated frequency f 50/60 Hz Operating range ± 10% Current inputs Rated current I Operating range (0-1.8) ×...
  • Page 55 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Binary inputs and outputs M12576-1 v13 IP15844-1 v1 Table 22. BIM - Binary input module Quantity Rated value Nominal range Binary inputs RL ±20% DC voltage, RL 24/30 V RL ±20% 48/60 V RL ±20% 110/125 V...
  • Page 56 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Table 24. IOM - Binary input/output module Quantity Rated value Nominal range Binary inputs RL ±20% DC voltage, RL 24/30 V RL ±20% 48/60 V RL ±20% 110/125 V RL ±20% 220/250 V Power consumption 24/30 V, 50 mA...
  • Page 57 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 M12318-1 v12 Table 25. IOM - Binary input/output module contact data (reference standard: IEC 61810-1) Function or quantity Trip and signal relays Fast signal relays (parallel reed relay) Binary outputs Max system voltage 250 V AC/DC 250 V DC Min load voltage...
  • Page 58 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 M12584-1 v12 Table 26. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-1) Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay) Binary outputs IOM: 10 IOM: 2...
  • Page 59 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 SEMOD175395-2 v12 Table 27. SOM - Static Output Module data (reference standard: IEC 61810-1): Heavy duty static binary outputs Function of quantity Static binary output trip Max system voltage 250 V DC Number of outputs Impedance open state High impedance...
  • Page 60 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Table 28. SOM - Static Output module data (reference standard: IEC 61810-1): Electromechanical relay outputs Function of quantity Trip and signal relays Max system voltage 250 V AC/DC Min load voltage 24 V DC Number of outputs Test voltage across open contact, 1 min...
  • Page 61 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 M12441-1 v12 Table 29. BOM - Binary output module contact data (reference standard: IEC 61810-1) Function or quantity Trip and Signal relays Binary outputs Max system voltage 250 V AC/DC Min load voltage 24 V DC Test voltage across open contact, 1 min 1000 V rms...
  • Page 62 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 GUID-61AA4AEF-D09C-4BA6-9142-B5CA857C0574 v1 The stated operate time for functions include the operating time for the binary inputs and outputs. Table 30. IRF - Internal Fail relay output Quantity Rated value Max. system voltage 250 V DC Min.
  • Page 63 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Table 32. Auxiliary DC supply voltage influence on functionality during operation Dependence on Reference value Within nominal Influence range Ripple, in DC auxiliary voltage max. 2% 15% of EL 0.01%/% Operative range Full wave rectified Auxiliary voltage dependence, operate ±20% of EL...
  • Page 64 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Type tests according to standards M16706-1 v15 IP15778-1 v1 Table 34. Electromagnetic compatibility Test Type test values Reference standards 1 MHz burst disturbance 2.5 kV IEC 60255-26 100 kHz slow damped oscillatory wave immunity test 2.5 kV IEC 61000-4-18, Level 3 Ring wave immunity test, 100 kHz...
  • Page 65 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Table 36. Environmental conditions Description Value Operating temperature range -25°C to +55°C (continuous) Short-time service temperature range -40°C to +70°C (<16h) Note: Degradation in MTBF and HMI performance outside the temperature range of -25°C to +55°C Relative humidity <93%, non-condensing Atmospheric pressure...
  • Page 66 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Differential protection GUID-246CE6FB-C1E5-4795-8687-E1591A897249 v1 Table 40. Busbar differential protection Function Range or value Accuracy Operating characteristic S=0.53 fixed ± 2.0% of I at I ≤ I ± 2.0% of I at I > I Differential protection operation level (100-50000) A ±...
  • Page 67 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Table 40. Busbar differential protection , continued Function Range or value Accuracy Independent time delay for slow open (1.00-600.00) s ± 0.2% or ± 25 ms whichever is greater CT alarm at 2 x OCTOperLev to 0 Independent time delay to force bay (0.000-60.000) s ±...
  • Page 68 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Current protection M12342-1 v23 Table 41. Directional phase overcurrent protection, four steps OC4PTOC Function Range or value Accuracy ±1.0% of I Operate current, step 1-4 (5-2500)% of lBase at I ≤ I ±1.0% of I at I >...
  • Page 69 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 SEMOD127584-2 v8 Table 42. Four step single phase overcurrent protection PH4SPTOC Function Setting range Accuracy Operate current, step 1 - 4 (5-2500)% of lBase ± 1.0% of I at I ≤ I ±...
  • Page 70 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 M15223-1 v18 Table 43. Directional residual overcurrent protection, four steps EF4PTOC Function Range or value Accuracy Operate current, step 1-4 (1-2500)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio >...
  • Page 71 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 GUID-E83AD807-8FE0-4244-A50E-86B9AF92469E v7 Table 44. Four step directional negative phase sequence overcurrent protection NS4PTOC Function Range or value Accuracy at I £ I Operate current, step 1 - 4 (1-2500)% of lBase ±1.0% of I ±1.0% of I at I >...
  • Page 72 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 M13266-2 v9 Table 45. Thermal overload protection, two time constants TRPTTR Function Range or value Accuracy Base current 1 and 2 (30–250)% of IBase ±1.0% of I Operate time: Time constant τ = (0.10–500.00) ±5.0% or ±200 ms whichever is greater minutes ∑...
  • Page 73 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 SEMOD127592-2 v8 Table 47. Breaker failure protection, single phase version CCSRBRF Function Range or value Accuracy at I £ I Operate phase current (5-200)% of lBase ± 1.0% of I ± 1.0% of I at I > I Reset ratio, phase current >...
  • Page 74 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 SEMOD175159-2 v9 Table 49. Directional overpower protection GOPPDOP Function Range or value Accuracy Power level (0.0–500.0)% of SBase ±1.0% of S at S ≤ S for Step 1 and Step 2 ±1.0% of S at S >...
  • Page 75 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 GUID-6A7DA510-E145-4C5B-A7DC-97BC4258E621 v10 Table 50. Capacitor bank protection CBPGAPC Function Range or value Accuracy Operate value, overcurrent (10-900)% of lBase ±2.0% of I at I ≤ I ±2.0% of I at I > I Reset ratio, overcurrent >95% at (100-900)% of IBase Start time, overcurrent, at 0.5 x Iset...
  • Page 76 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Voltage protection M13290-1 v16 Table 51. Two step undervoltage protection UV2PTUV Function Range or value Accuracy Operate voltage, low and high step (1.0–100.0)% of UBase ±0.5% of U Absolute hysteresis (0.0–50.0)% of UBase ±0.5% of U Internal blocking level, step 1 and step 2 (1–50)% of UBase...
  • Page 77 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 M13304-1 v15 Table 52. Two step overvoltage protection OV2PTOV Function Range or value Accuracy Operate voltage, step 1 and 2 (1.0-200.0)% of UBase ±0.5% of U at U ≤ U ±0.5% of U at U > U Absolute hysteresis (0.0–50.0)% of UBase ±0.5% of U...
  • Page 78 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 M13317-2 v16 Table 53. Residual overvoltage protection, two steps ROV2PTOV Function Range or value Accuracy Operate voltage, step 1 - step 2 (1.0-200.0)% of UBase ± 0.5% of U at U ≤ U ±...
  • Page 79 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 SEMOD175210-2 v7 Table 55. Loss of voltage check LOVPTUV Function Range or value Accuracy Operate voltage (1–100)% of UBase ±0.5% of U Pulse timer when disconnecting all three (0.050–60.000) s ±0.2% or ±15 ms whichever is greater phases Time delay for enabling the functions after (0.000–60.000) s...
  • Page 80 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Frequency protection M13360-1 v16 Table 56. Underfrequency protection SAPTUF Function Range or Value Accuracy Operate value, start function, at (35.00 - 75.00) Hz ±2.0 mHz symmetrical three phase voltage, StartFrequency Reset hysteresis 10.0 mHz fixed ±2.0 mHz Start time measurement...
  • Page 81 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 M14964-1 v13 Table 57. Underfrequency protection SAPTOF Function Range or Value Accuracy Operate value, start function, at (35.00 - 90.00) Hz ±2.0 mHz symmetrical three phase voltage, StartFrequency 10.0 mHz fixed ±2.0 mHz Reset hysteresis Start time measurement with sudden...
  • Page 82 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 M14976-1 v11 Table 58. Rate-of-change frequency protection SAPFRC Function Range and value Accuracy Operate value, start function, at Positive gradient: from 0.05 to 10.00 Hz/s ** ±10.0 mHz/s symmetrical three phase voltage *, Negative gradient: from -0.05 to -10.00 Hz/s ** StartFreqGrad or Gs per IEC 60255-181 standard...
  • Page 83 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Table 58. Rate-of-change frequency protection SAPFRC , continued Function Range and value Accuracy Disengaging time * fr = 50 Hz Gs: ±0.05 Hz/s Min. = 130 ms Tested frequency slope: Max. = 270 ms 1.2, 2.0, 5.0, 10.0 x Gs Gs: ±5.00 Hz/s Min.
  • Page 84 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Multipurpose protection M13095-2 v11 Table 59. General current and voltage protection CVGAPC Function Range or value Accuracy Measuring current input phase1, phase2, phase3, PosSeq, - NegSeq, -3*ZeroSeq, MaxPh, MinPh, UnbalancePh, phase1-phase2, phase2-phase3, phase3-phase1, MaxPh-Ph, MinPh-Ph, UnbalancePh- Measuring voltage input...
  • Page 85 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Table 59. General current and voltage protection CVGAPC, continued Function Range or value Accuracy Start undervoltage, step 1 - 2 (2.0 - 150.0)% of UBase ±0.5% of U at U ≤ U ±0.5% of U at U >...
  • Page 86 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Table 59. General current and voltage protection CVGAPC, continued Function Range or value Accuracy Impulse margin time 15 ms typically Undervoltage: Critical impulse time 10 ms typically at 1.2 x U to 0.8 x Impulse margin time 15 ms typically...
  • Page 87 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Secondary system supervision M16069-1 v13 Table 60. Fuse failure supervision FUFSPVC Function Range or value Accuracy Operate voltage, zero sequence (1-100)% of UBase ±0.5% of U Operate current, zero sequence (1–100)% of IBase ±0.5% of I Operate voltage, negative sequence (1-100)% of UBase...
  • Page 88 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 GUID-DAECF9F5-1D0B-43FC-AD29-8F96E05DD0DA v4 Table 62. Voltage based delta supervision DELVSPVC Function Range or value Accuracy Minimum Voltage (5.0 - 50.0)% of UBase ±0.5% of Ur at U ≤ Ur DelU> (2.0 - 500.0)% of UBase Instantaneous 1 cycle &...
  • Page 89 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Control M12359-1 v16 Table 64. Synchronizing, synchrocheck and energizing check SESRSYN Function Range or value Accuracy Phase shift, j (-180 to 180) degrees line Voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of UBase ±0.5% of U at U ≤...
  • Page 90 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 M12379-1 v14 Table 65. Autorecloser SMBRREC Function Range or value Accuracy Dead time: shot 1 “t1 1Ph” (0.000-120.000) s ±0.2% or ±35 ms shot 1 “t1 2Ph” whichever is greater shot 1 “t1 3Ph “ shot 1 “t1 3PhHS”...
  • Page 91 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Logic GUID-3AB1EE95-51BF-4CC4-99BD-F4ECDAACB75A v3 Table 66. Number of TMAGAPC instances Function Quantity with cycle time 3 ms 8 ms 100 ms TMAGAPC GUID-A05AF26F-DC98-4E62-B96B-E75D19F20767 v2 Table 67. Number of ALMCALH instances Function Quantity with cycle time 3 ms 8 ms 100 ms...
  • Page 92 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 GUID-B2E6F510-8766-4381-9618-CE02ED71FFB6 v2 Table 73. Number of LLD instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms GUID-35A795D7-A6BD-4669-A023-43C497DBFB01 v4 Table 74. Number of OR instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms...
  • Page 93 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 GUID-27DF23C0-A0B2-4BB0-80B5-FC7B7F7FE448 v1 Table 81. Number of INDCOMBSPQT instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms INDCOMBSPQT GUID-C1E61AE5-22CF-4198-97CF-8C8043EE96D2 v1 Table 82. Number of INDEXTSPQT instances Logic block Quantity with cycle time 3 ms 8 ms...
  • Page 94 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Table 89. Number of TIMERSETQT instances Logic block Quantity with cycle time Range or Value Accuracy 3 ms 8 ms 100 ms TIMERSETQT (0.000–90000.000) s ±0.5% ±10 ms GUID-1C381E02-6B9E-44DC-828F-8B3EA7EDAA54 v1 Table 90. Number of XORQT instances Logic block Quantity with cycle time 3 ms...
  • Page 95 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 GUID-B45901F4-B163-4696-8220-7F8CAC84D793 v3 Table 94. Number of IB16 instances Function Quantity with cycle time 3 ms 8 ms 100 ms IB16 GUID-7D6B459F-3050-41A6-A925-1F548AF0E29A v1 GUID-A339BBA3-8FD0-429D-BB49-809EAC4D53B0 v2 Table 95. Integer to Boolean conversion for six-zone busbar BCTZCONN Function Quantity with cycle time...
  • Page 96 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Table 98. Number of TEIGAPC instances Function Quantity with cycle time 3 ms 8 ms 100 ms TEIGAPC GUID-CEA332FF-838D-42B7-AEFC-C1E87809825E v4 Table 99. Number of INTCOMP instances Function Quantity with cycle time 3 ms 8 ms 100 ms...
  • Page 97 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Table 106. Number of ABS instances Function Quantity with cycle time 3 ms 8 ms 100 ms Table 107. Number of POL_REC instances Function Quantity with cycle time 3 ms 8 ms 100 ms POL_REC Table 108.
  • Page 98 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Monitoring M12386-1 v17 Table 114. Power system measurement CVMMXN Function Range or value Accuracy Frequency (0.8-1.2) x f ±5.0 mHz for U at 0.2 × U ≤ U < 0.5 × U ±3.0 mHz for U at 0.5 ×...
  • Page 99 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 GUID-ED634B6D-9918-464F-B6A4-51B78129B819 v6 Table 117. Voltage measurement phase-earth VNMMXU Function Range or value Accuracy Voltage (5 to 175) V ±0.5% of U at U ≤ 50 V ±0.2% of U at U > 50 V Phase angle (5 to 175) V ±0.5 degrees at U ≤...
  • Page 100 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 M12760-1 v13 Table 121. Disturbance report DRPRDRE Function Range or value Accuracy Pre-fault time (0.05–9.90) s Post-fault time (0.1–10.0) s Limit time (0.5–10.0) s Maximum number of recordings 200, first in - first out Time tagging resolution 1 ms See table...
  • Page 101 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 GUID-83B0F607-D898-403A-94FD-7FE8D45C73FF v9 Table 123. Insulation supervision for liquid medium function SSIML Function Range or value Accuracy Oil alarm level 1.00-100.00 ±10.0% of set value or 0.2 whichever is greater Oil lockout level 1.00-100.00 ±10.0% of set value or 0.2 whichever is greater Temperature alarm level...
  • Page 102 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 M12702-1 v6 Table 127. Event recorder Function Value Buffer capacity Maximum number of events in disturbance 1056 report Maximum number of disturbance reports Resolution 1 ms Accuracy Depending on time synchronizing M13747-1 v6 Table 128.
  • Page 103 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 GUID-09EC65AC-C60B-4256-A601-FE2CC90D26EC v3 Table 132. Current harmonic monitoring CHMMHAI (50/60 Hz) Function Range or value Accuracy Fundamental Harmonic Frequency (0.95 to 1.05) X f ±2 mHz order to 9 order (0.1 - 0.5) X I True RMS (0.2 to 2) X I None...
  • Page 104 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 GUID-74F6F38A-8DF9-4343-910D-4E0594C6E21F v1 Table 134. Fault current and voltage monitoring FLTMMXU - 50/60 Hz (8 ms application thread) Function Range or value Accuracy Voltage, FLTULxMAG (1 to 300) V ±0.5% of U at U ≤...
  • Page 105 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Metering M13404-2 v5 Table 135. Pulse-counter logic PCFCNT Function Setting range Accuracy Input frequency See Binary Input Module (BIM) Cycle time for report of counter (1–3600) s value SEMOD153707-2 v6 Table 136. Function for energy calculation and demand handling ETPMMTR Function Range or value Accuracy...
  • Page 106 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Station communication M15031-1 v9 Table 137. Communication protocols Function Value Protocol IEC 61850-8-1 Communication speed for the IEDs 100BASE-FX Protocol IEC 60870–5–103 Communication speed for the IEDs 9600 or 19200 Bd Protocol DNP3.0 Communication speed for the IEDs...
  • Page 107 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 M12589-1 v6 Table 142. SLM – LON port Quantity Range or value Optical connector Glass fiber: type ST Plastic fiber: type HFBR snap-in Fiber, optical budget Glass fiber: 11 dB (1000m/3000 ft typically *) Plastic fiber: 7 dB (10m/35 ft typically *) Glass fiber: 62.5/125 mm Fiber diameter...
  • Page 108 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Table 146. SFP - Galvanic RJ45 Quantity Rated value Number of channels Up to 6 single or 3 redundant or a combination of single and redundant links for communication using any protocol Standard IEEE 802.3u 100BASE-TX Type of cable...
  • Page 109 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Remote communication M12756-1 v14 Table 149. Line data communication module Characteristic Range or value Type of LDCM Short range (SR) Medium range (MR) Long range (LR) Type of fiber Multi-mode fiber Single-mode fiber Single-mode fiber glass 62.5/125 µm...
  • Page 110 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Hardware M11778-1 v8 SEMOD53385-1 v1 Table 151. Case Material Steel sheet Front plate Stainless steel with cut-out for HMI Surface treatment Aluzink preplated steel Finish Light grey (RAL 7035) M12327-1 v6 Table 152.
  • Page 111 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 GUID-96676D5D-0835-44DA-BC22-058FD18BDF34 v3 Because of limitations of space, when ring lug terminal is ordered for Binary I/O connections, one blank slot is necessary between two adjacent I/O modules. Please refer to the ordering particulars for details.
  • Page 112 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Basic IED functions M11963-1 v5 Table 159. Self supervision with internal event list Data Value Recording manner Continuous, event controlled List size 40 events, first in-first out M12331-1 v9 Table 160. Time synchronization, time tagging Function Value Time tagging resolution, events and sampled measurement values...
  • Page 113 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 SEMOD141136-2 v10 Table 164. IRIG-B Quantity Rated value Number of channels IRIG-B Number of optical channels Electrical connector: Electrical connector IRIG-B Pulse-width modulated 5 Vpp Amplitude modulated – low level 1-3 Vpp –...
  • Page 114 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Inverse characteristic M12388-1 v24 Table 165. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 999.00 ANSI/IEEE C37.112 , 1.5 x I ≤ I ≤ 20 x I ±2.0% or ±40 ms whichever is greater æ...
  • Page 115 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Table 166. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 999.00 IEC 60255-151, ±2.0% 1.5 x I ≤ I ≤ 20 x I or ±40 ms whichever is æ...
  • Page 116 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 GUID-19F8E187-4ED0-48C3-92F6-0D9EAA2B39BB v5 Table 168. ANSI Inverse time characteristics for Sensitive directional residual overcurrent and power protection Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 2.00 ANSI/IEEE C37.112 , 1.5 x I ≤...
  • Page 117 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Table 169. IEC Inverse time characteristics for Sensitive directional residual overcurrent and power protection Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 2.00 IEC 60255-151, ±5.0% 1.5 x I ≤...
  • Page 118 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 SEMOD116978-2 v11 Table 171. Inverse time characteristics for overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater æ...
  • Page 119 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Table 172. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater æ ö...
  • Page 120 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Table 173. Inverse time characteristics for residual overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater æ...
  • Page 121: Ordering For Customized Ied

    Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 24. Ordering for customized IED GUID-4DD44951-7FD8-4F3F-813E-A1224EFF46C8 v14 Table 174. General guidelines Guidelines Carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.
  • Page 122 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Table 178. Differential protection Position Table 179. Differential functions Function Function Ordering no Position Available Selected Notes and rules identification Busbar differential protection, 2 zones, three phase/8 bays BBP3PH8B 1MRK005904-ZK 0–1 Busbar differential protection, 2 zones, single phase/24 bays BBP1PH24B 1MRK005904-ZG...
  • Page 123 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Table 187. Frequency functions Function Function Ordering no Position Available Selected Notes and rules identification Underfrequency protection SAPTUF 1MRK005914-AC 0–10 Overfrequency protection SAPTOF 1MRK005914-BB 0–6 Rate-of-change of frequency protection SAPFRC 1MRK005914-CB 0–6 Table 188.
  • Page 124 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Table 197. Logic functions Function Function Ordering no Position Available Selected Notes and rules identification Configurable logic blocks Q/T 1MRK005922-MX 0–1 Extension logic package 1MRK005922-DB 0–1 Integer to Boolean conversion for six-zone busbar BCTZCONN 1MRK005922-VA 00/34...
  • Page 125 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Table 204. Mounting selection Mounting details with IP40 of protection from the front Ordering no Selection Notes and rules No mounting kit included 19" rack mounting kit for 1/2 x 19" case or 2xRHGS6 or RHGS12 1MRK002420-BB 19"...
  • Page 126 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Table 208. Maximum quantity of I/O modules, with compression terminals When ordering I/O modules, observe the maximum quantities according to the tables below. Note: Standard order of location for I/O modules is BIM-BOM-SOM-IOM-MIM from left to right as seen from the rear side of the IED, but can also be freely placed.
  • Page 127 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Table 210. Binary input/output module selection Binary input/output Ordering no Selection Notes and rules modules Slot position (front view/rear view) 1/2 case with 1 █ █ █ 3/4 case with 1 █...
  • Page 128 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Table 210. Binary input/output module selection, continued Binary input/output Ordering no Selection Notes and rules modules IOM 8 inputs, RL 1MRK000173-CE 220-250 VDC, 50mA, 10+2 output relays IOM 8 inputs, RL 1MRK000173-CF 220-250 VDC, 110mA, 10+2...
  • Page 129 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Table 211. Station communication, remote end serial communication and time synchronization selection Station communication, remote end Ordering no Selection Notes and rules serial communication and time synchronization Slot position (front view/rear view) Available slots in 1/2, 3/4 and 1/1 █...
  • Page 130: Ordering For Pre-Configured Ied

    Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 25. Ordering for pre-configured IED GUID-9CBBA802-8662-447A-AAA9-0CC7345E8629 v16 Guidelines Carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.
  • Page 131 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Software options Ordering no Notes and rules No option Four step phase overcurrent protection - 4 bays 1MRK004001-CF Four step phase overcurrent protection - 8 bays 1MRK004001-CG Four step single phase overcurrent protection - 12 bays 1MRK004001-CH Four step single phase overcurrent protection - 24 bays 1MRK004001-CK...
  • Page 132 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Power supply modules Ordering no Notes and rules Compression terminals 1MRK002960-GA Ringlug terminals 1MRK002960-HA Power supply module, 24-60 VDC 1MRK002239-AB Power supply module, 90-250 VDC 1MRK002239-BB Selection for position #7 Human machine hardware interface Case size Ordering no Notes and rules...
  • Page 133 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Binary input/output modules Ordering no Notes and rules For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used. Note: 1BIM and 1 BOM included in A20, A31 and B20. 2 BIM and 1 BOM included in B21 and B31 Slot position (front view/rear view) 1/2 case with 1 TRM █...
  • Page 134 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Station communication, remote end Ordering no Notes and rules serial communication and time synchronization modules Slot position (front view/rear view) Available slots in 1/2 and 3/4 case █ █ █ █ █...
  • Page 135: Ordering For Accessories

    Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 26. Ordering for Accessories Accessories IP15151-1 v1 External current transformer unit SEMOD123520-4 v5 Note: Only for REB670 B20, B21 and B31 3 pcs SLCE 8–1 summation transformers on apparatus plate (2U high), 1/1 A Quantity: 1MRK 000 643-EA 3 pcs SLCE 8–1 summation transformers on apparatus plate (2U high), 5/1 A...
  • Page 136 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 Protection cover M15040-3 v8 Protective cover for rear side of RHGS6, 6U, 1/4 x 19” Quantity: 1MRK 002 420-AE Protective cover for rear side of terminal, 6U, 1/2 x 19” Quantity: 1MRK 002 420-AC Protective cover for rear side of terminal, 6U, 3/4 x 19”...
  • Page 137 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 User documentation Specify the number of printed manuals requested Application manual Quantity: 1MRK 505 370-UEN ANSI Quantity: 1MRK 505 370-UUS Technical manual Quantity: 1MRK 505 371-UEN ANSI Quantity: 1MRK 505 371-UUS Commissioning manual Quantity: 1MRK 505 372-UEN...
  • Page 138 Busbar protection REB670 1MRK 505 373-BEN P Version 2.2 ANSI Quantity: 1MRK 511 398-UUS Cyber security deployment guideline Quantity: 1MRK 511 399-UEN Application guide, Communication set-up Quantity: 1MRK 505 382-UEN Reference information M2175-3 v4 For our reference and statistics we would be pleased to be provided with the following application data: Country: End user: Station name:...
  • Page 140 ABB Power Grids Sweden AB Grid Automation Products SE-721 59 Västerås, Sweden Phone +46 (0) 10 738 00 00 Scan this QR code to visit our website https://hitachiabb-powergrids.com/protection-control © 2017 - 2021 Hitachi Power Grids. All rights reserved...