ADF10S48B
AC-DC Converter Technical Manual V1.1
Electrical Specifications
Parameter
Protection characteristics
Input undervoltage protection
Protection threshold
Recovery threshold
Hysteresis
Input overvoltage protection
Protection threshold
Recovery threshold
Hysteresis
Output overvoltage protection
Output overcurrent protection
Output short circuit protection
Overtemperature protection
Baseplate
Hysteresis
Dynamic characteristics
Overshoot amplitude
Recovery time
Efficiency
100% load
50% load
Other characteristics
Remote On/Off voltage
Low level
High level
AUX
ENA
GLOBAL ENERGY EFFICIENCY SPECIALIST
Min.
Typ.
Max.
74
-
85
-
-
90
5
-
-
295
-
310
290
-
-
5
-
-
-
-
59.5
105
-
150
-
-
-
90
-
-
5
-
-
-
5
-
-
-
250
87.0
90.2
-
90.0
92.8
-
87.0
90.1
-
90.0
92.1
-
0
-
0.8
2.4
-
3.5
10
-
14
-
-
-
Unit
Notes & Conditions
V AC
-
V AC
V AC
V AC
-
V AC
V AC
V
Latch off
%
Self-recovery
Self-recovery;
-
The module is not damaged even with
long-term short circuits.
Self-recovery;
The overtemperature protection
°C
threshold is obtained by measuring
the temperature of the middle of the
°C
baseplate.
T
= 25°C, V
= 110/220 V AC;
A
in
%
Current change rate: 0.1 A/μs;
Load: 25%–50%–25%;
µs
50%–75%–50%
%
T
= 25°C, V
= 110 V AC; I
A
in
%
T
= 25°C, V
= 220 V AC; I
A
in
%
T
= 25°C, V
= 110 V AC; I
A
in
%
T
= 25°C, V
= 220 V AC; I
A
in
V
Negative logic
V
Auxiliary power output. Its output
V
current is less than 20 mA.
-
See Enable (ENA).
6
= 10.5 A
out
= 10.5 A
out
= 5.25 A
out
= 5.25 A
out