Siemens MICROMASTER 440 Operating Instructions Manual page 77

Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Issue 10/03
P1300 = 0
P1500 = 0
P1910 = 1
P3900 = 1
MICROMASTER 440
Operating Instructions
6SE6400-5AW00-0BP0
Control mode (enters the required control mode)
0
V/f with linear characteristic
1
V/f with FCC
2
V/f with parabolic characteristic
3
V/f with programmable characteristic
5
V/f for textile applications
6
V/f with FCC for textile applications
19
V/f control with independent voltage setpoint
20
Sensorless Vector control
21
Vector control with sensor
22
Sensorless Vector torque-control
23
Vector torque-control with sensor
Selection of torque setpoint *
(enters the source for the torque setpoint)
0
No main setpoint
2
Analog setpoint
4
USS on BOP link
5
USS on COM link (control terminals 29 and 30)
6
CB on COM link (CB = communications module)
7
Analog setpoint 2
Select motor data identification * (refer to Section 3.5.4)
0
Disabled
1
Identification of all parameters with parameter change.
These are accepted and applied to the controller.
2
Identification of all parameters without parameter change.
These are displayed but are not applied to the controller.
3
Identification of saturation curve with parameter change
Alarm A0541 (motor data identification active) is generated, and a
measurement is made at the next ON command.
End of quick commissioning (start of the motor calculation)
0
No quick commissioning (no motor calculations)
1
Motor calculation and reset of all of the other parameters, which
are not included in the quick commissioning (attribute "QC" =
no), to the factory setting.
2
Motor calculation and reset of the I/O settings to the
factory setting.
3
Only motor calculation. The other parameters are not reset.
NOTE:
For P3900 = 1,2,3 → P0340 is internally set to 1 and the appropriate
data calculated (refer to the parameter list P0340)
is displayed. This means that the control data (closed-loop control) is being
calculated and is then copied, together with the parameters, from the RAM into
the ROM. After quick commissioning has been completed, P3900 is re-displayed.
NOTE
After this, it is not permissible to disconnect the drive inverter from the line
supply as P1910 is not saved.
3 Functions
77