Table 3-15 Bico Parameters For Ramp-Function Generator - Siemens MICROMASTER 440 Operating Instructions Manual

Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Issue 10/03
Table 3-15
P1140
BI: RFG enable
P1141
BI: RFG start
P1142
BI: RFG enable setpoint
NOTE
The maximum frequency of the setpoint channel is set using parameter P1080.
In V/f mode the maximum frequency is 650 Hz.
In vector mode the maximum frequency it is limited to 200 Hz (r1084).
MICROMASTER 440
Operating Instructions
6SE6400-5AW00-0BP0
BICO parameters for ramp-function generator
Parameter
Description
The ramp-function generator output is set to 0 if the
binary signal = 0.
The ramp-function generator output keeps its actual
value if the binary signal = 0.
If the binary signal = 0, then the ramp-function
generator input is set to 0 and the output is reduced
to 0 via the ramp-function generator ramp.
3 Functions
127