GE MI-869 Instruction Manual page 297

Motor protection system/motor protection, control and management
Table of Contents

Advertisement

CHAPTER 4: SETPOINTS
4
Table 4-29: I
T CURVE TRIP TIMES (IN SECONDS)
MULTIPLIER
CURRENT (I/I
(TDM)
1.5
0.01
0.1975
0.10
1.9753
1.00
19.753
10.00
197.531
100.00
1975.31
600.00
11851.9
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
T
= reset time in seconds (assuming energy capacity is 100% and RESET is
RESET
"Timed")
)
pickup
2.0
3.0
4.0
0.0625
0.0123
0.0039
0.6250
0.1235
0.0391
6.250
1.235
0.391
62.500
12.346
3.906
625.00
123.46
39.06
3750.0
740.7
234.4
FLEXCURVES
The custom FlexCurves are described in detail in the FlexCurves section of this chapter. The
curve shapes for the FlexCurves are derived from the formulae:
Where:
T = operate time (in seconds),
TDM = Multiplier setting,
I = input current,
I
= Pickup Current setting,
pickup
T
= reset time in seconds (assuming energy capacity is 100% and RESET is
RESET
"Timed")
DEFINITE TIME CURVES
The Definite Time curve shape operates as soon as the Pickup level is exceeded for a
specified period of time. The base Definite Time curve delay is in seconds. The curve
multiplier of 0.05 to 600 makes this delay adjustable from 50 to 600000 milliseconds.
Where:
T = operate time (in seconds)
TDM = Multiplier setting
I = input current
I
= Pickup Current setting
pickup
T
= reset time in seconds (assuming energy capacity is 100% and RESET is
RESET
"Timed")
5.0
6.0
7.0
0.0016
0.0008
0.0004
0.0160
0.0077
0.0042
0.160
0.077
0.042
1.600
0.772
0.416
16.00
7.72
4.16
96.00
46.3
25.0
PROTECTION
8.0
9.0
10.0
0.0002
0.00015
0.0001
0.0024
0.0015
0.0010
0.024
0.015
0.010
0.244
0.152
0.100
2.44
1.52
1.00
14.65
9.14
6.00
4–179