GE MI-869 Instruction Manual page 35

Motor protection system/motor protection, control and management
Table of Contents

Advertisement

CHAPTER 1: INTRODUCTION
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CLOCK
Setup:........................................................................Date and Time, Daylight Saving Time, UTC (Coordinated
Backup Retention: ..............................................1 hour
IRIG-B INPUT
Auto-detect: ..........................................................DC and AM
Amplitude Modulation:.....................................1 V to 10 V pk-to-pk
DC Shift:...................................................................TTL
Input Impedance:................................................40 kΩ
Isolation:..................................................................2 kV
RTD INPUTS
Types (3-wire):.......................................................100 Ω Platinum, 120 Ω Nickel, 100 Ω Nickel, 10 Ω Copper
Sensing current:...................................................5 mA
Range: ......................................................................–40 to +250°C (-40 to +482°F)
Accuracy: ................................................................±2°C (±4°F)
Isolation:..................................................................36 V pk-pk (a group of RTDs to ground)
Lead Resistance: .................................................25 Ohms max. per lead for platinum or nickel and 3 Ohms
Universal Time)
max. per lead for copper RTDs
SPECIFICATIONS
1–25

Advertisement