Enter 1.00 to turn off the Trip Lead Level. The HMI also shows it is "OFF".
TRIP LAG LEVEL
Range: 0.05 to 1.00 in steps of 0.01
Default: 1.00
This setting specifies the Power Factor Lag Trip level.
When the Trip Lag Level is set to 1.00, the pickup level turns it off.
TRIP PICKUP DELAY
Range: 0.00 to 600.00 s in steps of 0.01 s
Default: 1.00 s
The setting specifies a time delay for the trip function.
TRIP DROPOUT DELAY
Range: 0.00 to 600.00 s in steps of 0.01 s
Default: 1.00 s
The setting specifies a dropout time delay for the trip function.
TRIP OUTPUT RELAY X
Range: Do Not Operate, Operate
Default: Do Not Operate
Any assignable output relay can be selected to operate upon Power Factor trip function.
ALARM FUNCTION
Range: Disabled, Alarm, Latch Alarm
Default: Disabled
This setting enables the Power Factor Alarm functionality.
ALARM LEAD LEVEL
Range: 0.05 to 1.00 in steps of 0.01
Default: 1.00
This setting specifies the Power Factor Lead Alarm level.
Enter 1.00 to turn off the Alarm Lead Level. The HMI shows "OFF".
ALARM LAG LEVEL
Range: 0.05 to 1.00 in steps of 0.01
Default: 1.00
This setting specifies the Power Factor Lag alarm level.
Enter 1.00 to turn off the Alarm Lag Level. The HMI shows OFF".
ALARM PICKUP DELAY
Range: 0.00 to 600.00 s in steps of 0.01 s
Default: 1.00 s
The setting specifies a time delay for the alarm function.
ALARM DROPOUT DELAY
Range: 0.00 to 600.00 s in steps of 0.01 s
Default: 1.00 s
The setting specifies a dropout time delay for the alarm function.