1MRS757275
3.4.6.
COM600 series, version 4.1
IEC 61850 Proxy Server User's Manual

Configuring GOOSE publishing

To send GOOSE data, you must first define the sending data set used by the GOOSE
control block and then create the control block.
1. Create a new Data Set. Rename it if you plan to use several different sets of data
(see 3.4.2.1, Dataset Editor).
Figure 3.4.6-1 Creating a new data set
2. Modify the data set to be sent with GOOSE.
Normally GOOSE data sets are configured to the attribute
level and only the value and quality are used (e.g.
Pos.stVal and Pos.q). Use the Enable daName for
GOOSE option and manually remove the unnecessary
attributes from the data set.