ABB COM600S User Manual page 28

Com600 series 4.1 release iec 61850 proxy server
Hide thumbs Also See for COM600S:
Table of Contents

Advertisement

28
COM600 series, version 4.1
IEC 61850 Proxy Server User's Manual
Figure 3.4.6-2 Modifying the data set to be sent with GOOSE
3. Create a new GOOSE Control Block (GoCB).
Figure 3.4.6-3 Creating GOOSE Control Block
4. Configure the GOOSE control block, see Figure 3.4.6-4.
Select the created data set.
Define APPID (Application Identifier) which is unique within the system. It
identifies the purpose of this particular dataset.
Define a multicast address to which the specific GOOSE data is sent. The
receiving IED understands which frames with a specific multicast address are
the interesting ones and starts to process them.
1MRS757275
modifying_dataset.png
creating_gcb.png